Heat & Glo LifeStyle CERONA-36, CERONA-42 Disassembly of Vent Sections, Horizontal Sections

Models: CERONA-42 CERONA-36

1 62
Download 62 pages 22.54 Kb
Page 25
Image 25

Securing the Vent Sections

Vertical Sections

Vertical sections of pipe must be supported every 8 feet after the 25 foot maximum unsupported rise. The vent support or plumber’s strap (spaced 120° apart) may be used to do this (see Figure 8.9).

Horizontal Sections

Horizontal sections of vent must be supported every 5 feet with a vent support or plumber’s strap.

B.Disassembly of Vent Sections

To disassemble any two pieces of pipe, rotate either section (see Figure 8.11), so that the seams on both pipe sections are aligned (see Figure 8.12). They can then be carefully pulled apart.

WARNING

Fire Risk. Explosion Risk. Combustion Fume Risk.

Use vent run supports per installation instructions.

Connect vent sections per installation instructions.

Maintain all clearances to combustibles.

Do NOT allow vent to sag below connection point to appliance.

Improper support may allow vent to sag or separate.

Figure 8.9 Securing Vertical Pipe Sections

Figure 8.10 Securing Horizontal Pipe Sections

Figure 8.11 Rotate Seams for Disassembly

Figure 8.12 Align and Disassemble Vent Sections

Heat & Glo • Cerona-36, Cerona-422106-900 Rev. A • 6/06

25

Page 25
Image 25
Heat & Glo LifeStyle CERONA-36, CERONA-42 Disassembly of Vent Sections, Securing the Vent Sections Vertical Sections