E. Hearth Extension
WARNING
Fire Risk.
Hearth extension required to protect combustible floors in front of appliance.
•An 8 inch minimum hearth extension must be constructed of
NAILING TABS (BOTH SIDES)
A
|
|
| B | |
|
|
|
| |
|
| A | B | |
in. | 8 | |||
mm | 1045 | 203 | ||
| ||||
| in. | 8 | ||
mm | 1222 | 203 | ||
|
Figure 3.6 Hearth Extension Dimensions
| 8 in. |
|
|
1 in. | (203 mm) |
|
|
(25 mm) |
|
|
|
WOOD OR OTHER | MARBLE, GRANITE, TILE OR | BOTTOM OF | |
COMBUSTIBLE |
| OTHER | |
FLOOR OR PLATFORM | HEARTH EXTENSION | FIREPLACE | |
Clearance to covered combustible hearth extension | |||
Figure 3.7 |
|
|
|
|
| MAY BE |
|
|
| COMBUSTIBLE |
|
|
| MATERIAL |
|
6 in.
(152 mm)5-1/4 in.
(133 mm)
| COMBUSTIBLES UP TO | |
WOOD OR OTHER | 1 INCH THICK ALLOWED | |
COMBUSTIBLE | UNDER THE OPENING | |
FLOOR OR | BOTTOM OF | |
FIREPLACE | ||
PLATFORM | ||
|
Clearance to exposed combustible hearth extension
(6 inch Minimum to top surface of combustible floor or floor covering.
Figure 3.8
10 | Heat & Glo • |