Heat & Glo LifeStyle CRESCENT II D. Vent Diagrams, Top Vent - Horizontal Termination, One Elbow

Models: CRESCENT II

1 54
Download 54 pages 34.89 Kb
Page 14
Image 14
D. Vent Diagrams

D. Vent Diagrams

1. Top Vent - Horizontal Termination WARNING

Fire Risk. Explosion Risk.

Do NOT pack insulation or other combustibles between ceiling firestops.

ALWAYS maintain specified clearances around venting and firestop systems.

Install wall shield and ceiling firestops as specified.

Failure to keep insulation or other material away from vent pipe may cause fire.

1. Top Vent - Horizontal Termination

One Elbow

V1 Minimum

H1

Maximum

Elbow only

2 ft

610 mm

 

 

6 in

152 mm

2 ft

610 mm

 

1 1/2 ft

457 mm

3 ft

914 mm

 

2 1/2 ft

762 mm

5 ft

1.5 m

 

3 1/2 ft

1067 mm

7 ft

2.1 m

V1

4 1/2 ft

1.4 m

15 ft

4.6 m

V1 + H1 = 38 ft (11.6 m) Maximum

H1

 

H1 = 15 ft (4.6 m) Maximum

Figure 5.3

Two Elbows

V1 Minimum

H1 + H2 Maximum

2 - 90º Elbows

Cannot do

back to back

 

 

6 in

152 mm

2

610 mm

1 1/2 ft

457 mm

3 ft

914 mm

2 1/2 ft

762 mm

5 ft

1.5 m

3 1/2 ft

1067 mm

7 ft

2.1 m

 

 

 

 

4 1/2 ft

1.4 m

15 ft

4.6 m

V1 + H1+ H2 = 38 ft (11.6 m) Maximum

H1 + H2 = 15 ft (4.6 m) Maximum

H2

V1

H1

 

 

INSTALLED

Figure 5.4

HORIZONTALLY

 

14

Heat & Glo • Crescent II • 2083-902 Rev. N • 7/09