Heat & Glo LifeStyle CRESCENT II C. Vertical Penetration Framing, Installing the Ceiling Firestop

Models: CRESCENT II

1 54
Download 54 pages 34.89 Kb
Page 18
Image 18
C. Vertical Penetration Framing

C. Vertical Penetration Framing

Installing the Ceiling Firestop WARNING

Fire Hazard

Keep loose materials or blown insulation from touching the vent pipe.

National building codes recommend using attic shield to keep loose materials/ blown insulation from contacting vent.

Hearth & Home Technologies requires the use of an attic shield.

Installing the Ceiling Firestop

Frame an opening 10 inches by 10 inches whenever the vent system penetrates a ceiling/floor (see Figure 6.3).

Frame the area with the same sized lumber as used in ceiling/floor joist.

When installing a top vent vertical termination appliance the hole should be directly above the appliance, unless the flue is offset.

Do not pack insulation around the vent. Insulation must be kept away from the pipe.

Installing Attic Shield

Note: An additional ceiling firestop is not required if attic shield is used.

Frame opening for attic shield.

Attic shield may be installed above or below ceiling (see Figure 6.4).

Secure with three fasteners on each side.

Fold tabs at top of attic shield in toward vent pipe. Tabs must keep vent pipe centered within shield.

Field construct additional shield height if insulation is deeper than height of attic shield.

ATTIC ABOVE

10 IN. (254 MM)

10 IN.

(254 MM)

HOLE SHOULD MEASURE

10 IN. X 10 IN.

(254 MM X 254 MM)

INSIDE TO INSIDE

Figure 6.3

BEND TABS IN

 

AROUND PIPE

 

3 FASTENERS

 

PER SIDE

 

ATTIC SHIELD INSTALLED

ATTIC SHIELD INSTALLED

BELOW CEILING

ABOVE CEILING

Figure 6.4 Installing the Attic Shield

 

18

Heat & Glo • Crescent II • 2083-902 Rev. N • 7/09

Page 18
Image 18
Heat & Glo LifeStyle CRESCENT II C. Vertical Penetration Framing, Installing the Ceiling Firestop, Installing Attic Shield