5 Fireplace Size Requirements

A. Minimum Fireplace Opening

Minimum fireplace opening requirements are shown in Figure 5.2.

WARNING! Risk of Fire or Burns! Provide adequate clearance around air openings and for service access.

Due to high temperatures, the appliance should be locat- ed out of traffic and away from furniture and draperies.

The firebrick (refractory), glass doors, screen rails, screen mesh and log grates can be removed from a factory built firebox in order to gain minimum gas insert opening requirements.

Any smoke shelves, shields and baffles may be removed from the factory built firebox if attached with mechanical fasteners.

The metal floor of the solid fuel firebox may be removed to facilitate the installation of the insert.

Cutting of any sheet metal parts of the fireplace in which the gas fireplace insert is to be installed is prohibited, except the floor as tested for and as noted above and in Figure 5.1.

A minimum 1/2 inch gap from the bottom of the appliance to the metal floor of the solid fuel firebox is RECOMMENDED for optimal fan performance. See side view in Figure 5.1.

SIDE VIEW

 

 

TOP VIEW

 

11-1/4

METAL FLOOR OF EXISTING

 

IN.

 

 

 

SOLID FUEL FIREBOX

 

 

 

5 IN.

 

REMOVE THIS

6 IN.

 

SECTION OF

12 IN.

 

METAL FLOOR

 

 

 

 

 

EXISTING FACTORY BUILT FIREBOX

1/2 IN. MINIMUM LEVELING HEIGHT

 

 

 

(RECOMMENDED)

11-1/4

 

ESCAPE-I35-C

1/4 IN. REQUIRED

 

IN.

 

ESCAPE-I30-C

METAL FLOOR OF EXISTING SOLID FUEL FIREBOX

 

 

 

 

 

 

5 IN.

 

REMOVE THIS

 

6 IN.

 

SECTION OF

 

12 IN.

 

METAL FLOOR

 

Figure 5.1-A

Figure 5.1-B

 

 

The appliance may not be placed directly on the base of the outer wrap, a 1/4 inch airspace MUST be provided between the insert and the floor of the outer wrap. Use the levelling legs to raise the insert a minimum of 1/4 inch. The original fireplace may never be returned to solid fuel in this condition. The sidewalls and top structure of the firebox may not be altered with the exception of removable baffles and dampers.

If the recommended 1/2 inch leveling leg height can not be achieved, a section of the factory-built metal floor may be removed. See Figure 5.1-B.

18

Heat & Glo • Escape-I35-C, Escape-I30-C2201-901 Rev. H • 5/12

Page 18
Image 18
Heat & Glo LifeStyle ESCAPE-I35-C owner manual Fireplace Size Requirements, Minimum Fireplace Opening