D. How to Use the Vent Graph

E. Venting Guidelines

1. Measure the distance from the top of appliance to the center of the 90° elbow. On the graph below, draw a horizontal line from that measurement on the vertical axis across until it intersects with the slanted line.

2.From the point of this intersection, draw a vertical line to the bottom of the graph.

3.The point at which this line meets the bottom line of the graph is the maximum length of the horizontal run.

Example 1: If the vertical dimension from the top of the appliance to the center of the 90° elbow is 7 ft. (2m), the horizontal run to the outer wall flange must not exceed 9 ft.-8 in. (3m).

.

Example 2: If the vertical dimension from the top of the appliance is 21 ft. (6m), the horizontal run to the outer wall flange must not exceed 4 ft.-3 in. (1m).

4.Each 90° elbow is equivalent to 3 ft. (914mm) of vent pipe and each 45° elbow is equivalent to 1 ft. (305mm) of vent pipe, and must be subtracted from vent pipe run. A single vertical to horizontal 90° elbow is already calculated into the allowable 15 ft. (5m) run. Each additional 90° elbow reduces the maximum horizontal distance by 3 ft. (914mm).

Example: The use of three elbows would reduce the allowable horizontal run to 9 ft. (3 - 1 = 2 elbows x 3 ft. = 6 ft.; 15 ft. max. - 6 ft. = 9 ft. max.)

Notes:

The maximum horizontal vent run is 15 ft. (5m) when the vertical vent rise is 10 ft. (3m).

Horizontal sections require a 1/4 in. (6mm) rise for every 12 in. (305mm) of horizontal travel.

Exterior vent diameter = 6-5/8 in. (168mm); Inner vent diameter = 4 in. (102mm).

Horizontal sections require noncombustible support every 3 ft. (914mm) , e.g. wall straps.

For any vertical termination a minimum of 6 ft. (2m) vertical must be used.

EXCEPTIONS FOR HORIZONTAL INSTALLATIONS: *The maximum horizontal vent run is 30 in. (762mm).

*The maximum horizontal vent run with a 45° elbow is 18 in. (457mm).

*No external minimum rise is required.

*The minimum horizontal vent run is 6 in. (152mm).

 

 

Termination cap

 

 

 

 

 

25 ft. (8m)

25'

 

 

 

 

 

 

 

NOTE: In the Commonwealth of Mas-

Maximum Vertical

 

 

 

 

 

 

 

sachusetts the word damper shall be

24'

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

replaced with the words flue restrictor.

 

22'

 

 

 

 

 

 

 

Example 2

 

 

 

 

 

 

 

 

 

20'

Adjust

 

 

 

 

 

 

 

 

18'

 

 

 

 

 

 

 

 

Intake

 

 

 

 

 

 

 

VERTICAL DISTANCE

16'

Damper

 

 

 

 

 

 

 

FROM APPLIANCE TO

 

 

 

 

 

 

 

 

90° ELBOW

14'

 

 

Install Flue

 

 

 

 

 

12'

 

 

 

 

 

 

 

 

 

Restrictor

 

 

 

 

 

10'

 

 

 

 

 

 

 

 

Example 1

8'

 

 

 

 

 

 

 

Termination cap

 

 

 

 

 

 

 

 

6 ft. (2m) Minimum

6'

 

 

 

 

 

 

 

 

Vertical Termination

4'

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

2'

 

 

 

 

 

 

 

 

C

 

 

 

 

 

 

 

 

 

L

 

2'

4'

6'

8'

10'

12'

14'

15'

 

 

 

 

 

 

SLK-01TRD or an approved Termination Cap

6 in. (152mm) Minimum starter pipe

Figure 5.2

30 in. (762mm) Maximum Horizontal run with no vertical pipe and with 1/4 in. (6mm) rise per foot. Must use approved Termination Cap.