Heat & Glo LifeStyle VRT-GY-N-AUB owner manual Burner Ignition and Operation, Frequency: Annually

Models: VRT-BZ-P-AUB VRT-GY-N-AUB VRT-BZ-N-AUB VRT-GY-P-AUB

1 75
Download 75 pages 49.02 Kb
Page 16
Image 16
Burner Ignition and Operation

Burner Ignition and Operation

Frequency: Annually

By: Qualified Service Technician

Tools needed: Protective gloves, vacuum cleaner, whisk broom, flashlight, voltmeter, indexed drill bit set, and a manometer.

Verify burner is properly secured and aligned with pilot or igniter.

Clean off burner top, inspect for plugged ports, corrosion or deterioration. Replace burner if necessary.

Replace Glowing embers with new dime-size pieces. DO NOT block ports or obstruct lighting paths.

Verify batteries have been removed from battery back-up IPI systems to prevent premature battery failure or leaking.

Check for smooth lighting and ignition carryover to all ports. Verify that there is no ignition delay.

Inspect for lifting or other flame problems.

Verify air shutter setting is correct. See Section 9 for required air shutter setting. Verify air shutter is clear of dust and debris.

Inspect orifice for soot, dirt and corrosion. Verify orifice size is correct. See Service Parts List for proper orifice sizing.

Verify manifold and inlet pressures. Adjust regulator as required.

Inspect pilot flame pattern and strength. See Figure 3.1 for proper pilot flame pattern. Clean or replace orifice spud as necessary.

Inspect IPI flame sensing rod for soot, corrosion and deterioration. Polish with fine steel wool or replace as required.

Verify that there is not a short in flame sense circuit by checking continuity between pilot hood and flame sensing rod. Replace pilot as necessary.

Figure 3.1 IPI Pilot Flame Patterns

16

Heat & Glo • VRT-AUB2123-980 Rev. H • 5/12

Page 16
Image 16
Heat & Glo LifeStyle VRT-GY-N-AUB, VRT-GY-P-AUB, VRT-BZ-P-AUB owner manual Burner Ignition and Operation, Frequency: Annually