6 Termination Locations
A. Vent Termination Minimum Clearances
WARNING
Fire Risk.
Maintain vent clearance to combustibles as specified.
• DO NOT pack air space with insulation or other materials.
Failure to keep insulation or other materials away from vent pipe may cause overheating and fire.
HORIZONTAL
OVERHANG
A | B |
6 in. (minimum) up to 20 in. | 18 in. minimum |
(152 mm (minimum) up to 508 mm) | (457 mm minimum) |
20 in. and over | 0 in. minimum |
(508 mm and over) | (0 mm minimum) |
Gas, Wood or Fuel Oil
Termination Cap
B
A*
Gas
24 in MIN. | 20 in MIN. |
(510 mm MIN.) | |
(610 mm MIN.) |
|
LOWEST
DISCHARGE
OPENING
TERMINATION CAP
VERTICAL
WALL
Termination
Cap **
* If using decoratuve cap cover(s), this distance may need to be increased. |
Refer to the installation instructions supplied with the decorative cap cover. |
12 in X
(305 mm)
ROOF PITCH IS X/ 12 in.
(305 mm)
H (MIN.) - MINIMUM HEIGHT FROM ROOF TO LOWEST DISCHARGE OPENING
Angle | H (Min.) mm |
500* | |
500* | |
500* | |
610* | |
760 | |
990 | |
1220. | |
1520. | |
1830. | |
2130. | |
2290. | |
2440. |
*910 mm minimum in snow regions
Figure 6.1 Minimum Height From Roof To Lowest Discharge Opening
**In a staggered installation with both gas and wood or fuel oil terminations, the wood or fuel oil termination cap must be higher than the gas termination cap.
Figure 6.2 Staggered Termination Caps
Heat & Glo • | 21 |