8 Vent Clearances and Framing
A. Pipe Clearances to Combustibles
WARNING! Risk of Fire! Maintain air space clearance to vent. DO NOT pack insulation or other combustibles:
•Between ceiling firestops
•Between wall shield firestops
•Around vent system
Failure to keep insulation or other material away from vent pipe may cause over heating and fire.
Note: Heat shields MUST overlap by a minimum of
•If wall thickness is less than 4 in. (102 mm) the existing heat shields must be field trimmed.
B. Wall Penetration Framing
Combustible Wall Penetration
Whenever a combustible wall is penetrated, you must frame a hole for the wall shield firestop(s). The wall shield firestop maintains minimum clearances and prevents cold air infiltration.
• | The opening must be framed on all four sides using the |
| same size framing materials as those used in the wall |
| construction. |
• SLP pipe - A wall shield firestop must be placed on each | |
| side of an interior wall. A minimum |
| overlap of attached heat shields must be maintained. |
• | See Section 10.H for information for regarding the in- |
3 in. (76 mm) top clearance
1 in. (25 mm) clearance around vertical sections
Heat
Shield
Wall
Shield
Firestop
3 in. (76 mm) top clearance *
Heat
Shield
1 in. (25 mm) clearance bottom & sides
stallation of a horizontal termination cap. |
Non-Combustible Wall Penetration
If the hole being penetrated is surrounded by noncom- bustible materials such as concrete, a hole with diameter one inch greater than the pipe is acceptable.
Whenever a
WALL
Heat
Shield
Wall
Shield
Firestop
3 in. (76 mm) top clearance *
Heat
Shield
1 in. (25 mm) clearance bottom & sides
Note: A 6 in. (152 mm) section of straight flue must be attached to the fireplace before a 90° elbow.
* Unit shown with
WALL
* When using SLP pipe, minimum clearances from the vent pipe to combustible
materials at inside wall firestops are: Top:
Figure 8.1 Horizontal Venting Clearances To Combustible
Materials
10 in.
(254 mm)
10 in.
(254 mm)
A* B*
10in.
(254 mm)
10in.
(254 mm)
C
D
|
| A* | B* | C | D | |
Inches | 69.3 | 68.3 | ||||
Millimeters | 1761 | 883 | 1736 | 857 | ||
| ||||||
Inches | 69.3 | 68.3 | ||||
Millimeters | 1761 | 883 | 1736 | 857 | ||
|
*Shows center of vent framing hole for top or rear venting. The center of the hole is one 1 in. (25.4 mm) above the center of the horizontal vent pipe.
Figure 8.2 Wall Penetration
Heat & Glo • | 37 |