Heat Controller RAD-81A, RAD-101A, RADS-81B MODEL BG8000ER, WG8000RY4, WG1000RY4, Possible Trouble

Models: RADS-81B RAD-81A RAD-101A

1 39
Download 39 pages 44.62 Kb
Page 31
Image 31
■MODEL : BG8000ER, WG8000RY4, WG1000RY4

Troubleshooting Guide

MODEL : BG8000ER, WG8000RY4, WG1000RY4

ELECTRIC PARTS TROUBLESHOOTING GUIDE:

Possible Trouble 1

Is the Trans input power AC 115V?

YES

Is the Trans output power

about AC 14V?

YES

Is output Voltage of IC01D

DC 12V?

YES

Is output Voltage of IC02D

DC 5V?

YES

• The unit does not operate.

NO

 

• Check the Fuse.

 

 

 

 

 

 

• Check the wiring diagram.

 

 

 

 

 

 

 

 

 

 

 

NO

 

NO

 

• Check the Main

 

 

 

 

 

Is shorted the Trans. output?

 

 

P.W.B pattern.

 

 

 

 

 

 

 

 

 

 

YES

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

• Exchange the Trans.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

NO

 

 

 

 

 

Exchange D02D~D05D.

 

 

 

 

 

 

 

• Exchange IC01D.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

NO

• Exchange IC02D.

 

Is the reset circuit all right?

(The No.14 of Micom

is 5V.)

YES

Is the

connection between

Main and Display

all right?

YES

NO

NO

ELECTRIC PARTS TROUBLESHOOTING GUIDE: • Exchange IC01A.

Connect connector exactly.

Is the voltage No.18 of Micom

NO

 

• Check the P.W.B

 

 

 

 

 

 

pattern.

 

 

 

 

DC 5V?

 

 

 

 

 

 

 

 

 

YES

Exchange Main P.W.B Ass'y.Possible Trouble 1Manual background