Heatiator C40 owner manual B. Clearances, 2 Clearances to Combustible Materials

Models: C40

1 71
Download 71 pages 48.08 Kb
Page 36
Image 36
B. Clearances

B. Clearances

Warning! Risk of Fire! You must comply with all minimum air space clearances to combustibles as specified in Fig- ure 6.2. Do NOT pack required air spaces with insulation or other materials.Framing or finishing material used on the front of, or in front of, the appliance closer than the minimums listed.must be constucted entirely of non-combustible mate- rials (i.e., steel studs, concrete boaed, etc.). Failure to comply may cause fire.

Storm Collar

Roof Flashing

2 in. min.Figure 6.2 Clearances to Combustible Materials

(51 mm)

(attic)

2 in. (51 mm) min. Manual background Ceiling Firestop

Manual backgroundManual background 2 in. (51 mm) min.

Attic

Insulation

Shield

Ceiling Firestop

(ceiling)

Manual backgroundManual background2 in. (51 mm) min.

Offset/Return with Manual background hanger straps

(ceiling)

2 in. (51 mm) min.

0 in. to level Manual background of standoffs Manual background

Manual background 2 in. (51 mm) min.

Must have 2 in. (51 mm)

minimum clearance

to header

0in.

to floor

1 in. (25 mm) to back of appliance

Manual backgroundManual background 1 in. (25mm) to side of appliance (except at nailing flanges where it is 1/2 in. [13 mm])

Figure 6.2 Clearances to Combustible Materials

NOTICE: Chimney air kit is not shown, but is required.