F. Mantel
A combustible mantel may be positioned no lower than 60 in. (1524mm) from the base of the fireplace.
The combustible mantel may have a maximum depth of 12 in. (305mm). Combustible trim pieces that project no more than 3/4 in. (19mm) from the face of the fireplace can be placed no closer than 6 in. (152mm) from the side of the decorative front. See Figure 10.13
Combustible trim must not cover:
•the metal surfaces of the fireplace
•where the
•the space between the metal face of the fireplace and framing members.
Refer to page 37 for clearance requirements
Mantel | Clearances are |
| from bottom of |
| appliance to lower |
| edge of mantel or |
Trim | trim |
60in.
(1524mm)
48in.
(1219mm)
Figure 10.13 Mantel Specifications