Heatiator C40 owner manual D. Electrical Access and Wiring Diagram, WARNING! Fire Risk

Models: C40

1 71
Download 71 pages 48.08 Kb
Page 38
Image 38
D. Electrical Access and Wiring Diagram

D. Electrical Access and Wiring Diagram

NOTICE: The manual override switch, rheostat speed con- trol and cover plate are supplied. You will need to supply: 14-3 wire with ground; 14-2 wire with ground; standard wall mount junction box; wire nuts.

1.Remove junction box cover plate on the bottom right side of the fireplace.

2.Thread the 14-3 with ground wire through the opening with the strain relief on the cover plate.

3.Match colors to wire harness, (red to red, white to white, etc) and secure with wire nuts.

NOTICE: Wiring for fans must be done before framed enclosure is completed. If using a Heat Zone kit, it also must be installed before enclosure is complete.

WARNING! Fire Risk!

Do not apply combustible finishing materials over any part of the front of this fireplace.

The metal fireplace face may only be covered with noncombustible materials such as ceramic tile, brick, or stone.

Do not cover or block any cooling air slots.

The decorative fascia must be removable for future service- ability of the Automatic Combustion Control.

Maintain clearances.

Use only non-combustible material below standoffs, material such as cement board is acceptable.

Framing or finishing material used on the front of, or in front of, the appliance closer than the minimums listed, must be constructed entirely of noncombustible materials (i.e., steel studs, concrete board, etc.).

Standard wall mount with

Junction Box

14-2 w/ground

WARNING! Fire Risk!Manual background14-3 w/ground

Match colors to wire Manual background harness (red to red,

white to white, etc) and secure with a wire nut

Power to the Fireplace

Snap Disc bypass switch

Figure 6.4 Fan Wiring Diagram

WHITE

RED Manual background

BLACK

WIRE NUT

WHITE

Manual background GREEN Manual backgroundManual backgroundManual backgroundManual backgroundManual backgroundManual backgroundManual backgroundManual background BLACK

Incoming Power

(110V)

Warning! Risk of Fire! You must comply with all minimum air space clearances to combustibles. Do NOT pack re-

quired air spaces with insulation or other materials.

WARNING! Fire Risk!

Comply with all minimum clearances specified.

A minimum 1 in. (13mm) air clearance must be maintained at the back and 1 in. (25mm) to the sides of the fireplace assembly.

Chimney sections at any level require a 2 in. (51mm) minimum air space clearance between the framing and chimney section.

Page 38

Heatilator • Constitution EPA Fireplace • 480-1091H

4/12

Page 38
Image 38
Heatiator C40 owner manual D. Electrical Access and Wiring Diagram, WARNING! Fire Risk