INSTALLATION
1.Remove the knockout or cover plate from the top of the fireplace and discard it. See Figure 11.2.
2.Cut a 3 in. (76mm) hole in the insulation board as per the dimensions shown in Figure 11.2
|
|
|
| |
| (97mm) |
|
|
|
Adapter |
|
|
| |
C |
|
|
| |
|
|
|
| |
L |
|
|
|
|
| Mounting |
|
|
|
| Plate |
|
|
|
| Starter Pipe |
| ||
| Knockout |
|
| |
|
|
|
| hole |
|
|
| .(76mm) | |
| Cuta | 3in | board | |
| ininsulation |
| ||
Figure 11.2 |
|
|
|
|
3.Determine the necessary length of starter pipe from the following table and cut as required. See Figure 11.3.
4.The starter pipe is shipped flat. After cutting to the required length, manually roll the pipe together and snap lock into place. NOTE: It is important the pipe length be adhered to or it will affect the performance of your fireplace.
Run Length | Cut Pipe | |
20 | - 40 ft | 2 in. (51mm)* |
| *A minimum of 2 in. (51mm) pipe must be used to | |
| cover the raw insulation to prevent it tfrom blow- | |
| ing out through the Return Air Grille. | |
10 | - 20 ft (3 - 6m) | 8 in. (203mm) |
3 | - 10 ft (1 - 3m) | No cut needed** |
**Use full 16 in. (406mm) as supplied
Figure 11.3
Figure 11.4
5.Slide the starter pipe into the fireplace, matching the holes in the plate to the holes in the fireplace.
6.Place the Adapter on the Mounting Plate lining up holes. Using the 4 sheet metal screws included in the kit, secure the Adapter and Mounting Plate into fireplace. After secur- ing to the fireplace, tape down the Adapter edges to the top of the fireplace with aluminum tape to prevent leakage.
7.Determine the location for the air register and fan housing assembly. Cut a
NOTICE: The fan and electrical connections must be accessible for servicing per local code requirements.
NOTE: If the fan housing is installed in a 2 x 4 wall, the front of the housing will protrude approximately 1/4 in. (6mm) from the finished wall. See Figure 11.5 on page 61.
8.Attach enough 6 in. (152mm)
Also screw the
Warning Fire Risk!
Comply with all minimum clearances specified.
•A minimum 1 in. (13mm) air clearance must be maintained at the back and 1 in. (25mm) to the sides of the fireplace assembly.
Page 60 | Heatilator • Constitution EPA Fireplace • | 4/12 |