Heatiator C40 D. Assemble the Chimney Sections, E. Installing CAK4A and Flex Pipe, Notes

Models: C40

1 71
Download 71 pages 32.62 Kb
Page 45
Image 45
D. Assemble the Chimney Sections

D. Assemble the Chimney Sections

Use only those components described in this manual.

Substitute or damaged chimney components could impair safe operation and cause overheating and fire.

Attach either a straight chimney section or an offset to the top of the fireplace (depending on your installation require- ment). Chimney sections are locked together by pushing downward until the top section meets the stop bead on the lower section.

The inner flue is placed to the inside of the flue section be- low it. The outer casing is placed outside the outer casing of the chimney section below it. See Figure 8.4.

Notice: Chimney sections cannot be disassembled once locked together. Plan ahead!

Lock chimney sections and/or offsets/returns together by pushing downward until the top section meets the stop bead on the lower section.

Pull on the top section to make sure it is fully engaged and will not separate.

You may use #6 or #8 sheet metal screws no longer than 1/2 in. (13 mm) to fasten chimney sections together. Do NOT penetrate inner flue.

Warning! Risk of Fire! You MUST use screws (provid- ed) to fasten offset/returns to chimney sections to keep the chimney parts from twisting. Failure to do so could cause fire.

Fasten offset/returns to chimney sections. Insert the screws (provided) through the predrilled holes. Do NOT penetrate inner flue.

Secure chimney returns with hanger straps provided; fasten to studs or joists.

Vertical straight runs of chimney must be supported every 35 ft (10.7 m).

Figure 8.4 Assembling Chimney Sections

Warning! Risk of Fire! Do NOT install substitute or dam- aged chimney components.

E. Installing CAK4A and Flex Pipe

NOTICE: Chimney Air Kit, Part CAK4A is required when using the SL-300 Pipe Series. Detailed instructions are supplied with the kit.

1.Install the chimney pipe first.

2.Hand bend the tabs in position before placing on the fireplace.

3.Place the box on top of the fireplace around the chimney pipe, push both pieces together and secure with screws provided.

4.Use the pre-punched holes in the tabs as guides and drill holes through the fireplace top.

5.Secure the CAK4A in place.

6.Seal around the kit at the flue and at the top of the can with caulk.

Attach

Flue First

Secure with Screws

Provided

CAK4A

Push Together

Secure to Top

Figure 8.5 Installing the CAK4A

NOTES:

1.The outside termination cap must be a minimum of 6 ft

(1829 mm) above the ground and kept free of debris.

2.If the CAK4A is installed in a chase, the CAK4A side termination cap must be at least 3 ft (914 mm) below the chimney top.

3.Seal around the cap and flex with caulk to stop air from getting in to the chase (See Figures 9.4-9.8 on page

52).

WARNING! Fire Risk!

The flex hose must never be compressed or deformed!

4/20/11

Heatilator • Constitution EPA Fireplace • 480-1091D

Page 45

Page 45
Image 45
Heatiator C40 owner manual D. Assemble the Chimney Sections, E. Installing CAK4A and Flex Pipe, Notes, WARNING! Fire Risk