B. Install Fireplace & Chimney

B. Install Fireplace & Chimney

TR344 Round Termination Cap

Install as per Sections 7 and 8.

C. Install Chase Top

You MUST use a chase top in a chase installation. Chase tops are available from your Heatilator dealer or may be field constructed.

Include a turndown and drip edge to prevent water from seeping into the chase.

Include a 2 in. (51 mm) soldered, welded or spun collar around pipe opening to keep water out.

Provide a 1/8 in. (3 mm) gap around the flue pipe.

Slope the chase top downward away from the opening.

Warning! Risk of Fire! Do not caulk the pipe to the chase top collar.

Caulk all seams to prevent leaks.

Termination

Cap

Slip

storm collar

around chimney pipe

before termination cap pipe is snapped into the chimney pipe.

Caulk gaps between

Storm

storm collar & pipe,

Collar

and storm collar

 

& chase top.

 

Collar

 

2 in. (51 mm)

Chimney

Minimum Height

Pipe

 

Chase Top

 

Do NOT

block air holes

6 in. (153 mm) Minimum top of chase to top of chimney pipe

Slope Downward (1/4 in. per foot minimum)

2 in. (51 mm) Collar on Chase Top

C. Install Chase Top Turn-down

D. Install Termination Cap Drip Edge

Manual background Chase

.018 (26 ga) min. Galvanized Chase Top

Figure 9.3 Chase Top Construction

D. Install Termination Cap

Install the chimney sections up through the chase enclo- sure.

Caulk the overlap seam of any exposed pipe sections that are located above the roof line to prevent leaks.

Refer to termination cap instructions.

Warning! Risk of Fire! The minimum overlap of cap to pipe (as shown in the following illustrations) MUST be met or chimney may separate from cap. Separation allows sparks, heat and embers to escape.

Notice: Paint the termination cap with a rust-resistant paint to protect against the effects of corrosion on those parts exposed to the weather.

Chase

Termination cap pipe and chimney section must be snapped together to maintain an overlap of 1-1/2 in. (38 mm).

Figure 9.4 Installing a TR344 Round Termination Cap

TR342 Round Telescoping Termination Cap

Assemble

Termination

storm collar

Cap

around extended

 

termination cap

 

pipe

 

once cap is

 

installed.

Do NOT

Caulk gaps between

block air

holes

storm collar & pipe,

Storm

and storm collar

Collar

& chase top.

3 clip brackets.

 

Slip over chase collar

 

and attach with screws

 

provided.

Collar

 

2 in. (51 mm)

14 1/2 in. (368 mm)

Minimum Height

Maximum

 

Chase Top

 

Chase

Chimney

Pipe

Termination cap pipe and chimney section must overlap 1-1/2 in. (38 mm)

Figure 9.5 Installing a TR342 Round Telescoping Termination Cap