11 Finishing
A. Mantel Projections
Figure 11.1 shows the minimum vertical and corresponding maximum horizontal dimensions of appliance mantels or other combustible projections above the top front edge of the appliance.
B. Facing Material
WARNING
Fire Risk
Do NOT obstruct air inlet or outlet grilles.
Do NOT modify grilles.
5
4
3
5
to ceiling
|
|
|
|
|
|
| 18 | |||
|
|
| 16 | 17 |
| |||||
|
|
|
| |||||||
|
|
|
|
| 16 | |||||
|
|
|
| |||||||
| 14 | 15 |
| 15- |
| 1/4 |
| |||
|
| |||||||||
13 |
|
| 14- | 1/2 |
|
|
| |||
| ||||||||||
|
| 13- |
| 3/4 |
|
|
|
|
| |
|
|
|
|
|
| |||||
12 | 13 |
|
|
|
|
|
|
|
|
11
10
9
8 |
|
| 10 |
| |||
7 | 9- |
| 1/4 |
6
Measured from top of hood (in inches)
•Modifying or covering grilles could cause temperature rise and fire hazard.
Finishing materials must not interfere with:
•Air flow through grilles or louvers.
•Operation of louvers or doors.
•Access for service.
Finish wall material may be combustible - Top and Sides
0 in.
Figure 11.1 Clearances to Mantels or other Combustibles above Appliance.
Top of
Appliance
Drywall
A
48 in.
(1219 mm)
B max.
Mantel Leg or Perpendicular Wall
A1 in. (25 mm) min. to perpendicular wall
B
Figure 11.2 Mantel Leg or Wall Projections (Acceptable on both sides of opening)
0 in. | 0 in. |
High Temperature Sealant (300° F/149° C min.)
Top and Side Seal Joint
Figure 11.3 Noncombustible Facing Diagram
WARNING
Fire Risk
Finish all edges and fronts to clearances and specifications listed in manual.
•Metal appliance front may be covered with non- combustible material only.
•Do NOT overlap combustible materials onto appliance front.
•Install combustible materials only up to specified clearances on top, front and sides.
•Seal joints between the finished wall and appliance top and sides using only a 300° F minimum sealant.
24 | Heatilator • Novus |