Hisense Group KF-5002GWE manual REFRIGERANT TUBE 5.1 Flaring the tube, Connection of the tubes

Models: KF-5002GWE

1 29
Download 29 pages 6.02 Kb
Page 29
Image 29
5.REFRIGERANT TUBE

Appendix: Installation

5.REFRIGERANT TUBE

5.1 Flaring the tube

(1)Cut the tube with a tube cutter to the desired length (30.50cm is recommended)

(2)Smooth the edge of the copper tube with a reamer or a file. Hold the pipe vertically with one end downward to make sure that no copper scraps fall into the copper tube.

Copper

Before

 

After

5.2 Connection of the tubes tube

5.3 Heat insulation of the refrigerant tube Reamer

Figure 18a

Figure 18b

(3)Put the tube flarer on the copper tube.

(4)Flare the copper tube ( Figure 19)

Tapered nuts

5.4 Wrapping the tubes Copper tube

Flarer

Figure 19

Note: The flared tube should have:

5.5 Ending of installation Smo oth internal surface

5.6 Discharge gas Smooth edges

Manual background C onsistent length of the tapered surface

5.2 Connection of the tubes

(1)The sealing tube must be used to prevent dust or water from getting into the tube.

(2)Before connecting the tube, apply some refrigerant oil on the surface of the flared tube and connections to prevent air leakage.( Figure 20)

(3)Align the connecting tube and the flared tube, and then turn the tapered nut to connect tightly. (Figure 21)

Application

of refrigerant oil Connecting Flared tube tube

Figure 21

(4) Fasten the nuts with a spanner.

5.3 Heat insulation of the refrigerant tube

All refrigerant tubes must be insulated heat with at least 8mm thick insulation materials. (Figure 22)

Heat insulation materials

Min. 8mm

Thickness

of 8mm

 

 

Figure 22

5.4 Wrapping the tubes

(1)Tie the two refrigeration tubes (including electrical wire if permitted as regulated), water drainage hose with white tape.

(2)Wrap half of the tubes outside the room starting from the end. (Figure 23)

Clip

Covering tubes with heat insulation materials

Figure 23

(3)Fix the wrapped tubes on the wall in clips with a space of 120cm.

Note: Do not tie the tubes too tight as this may reduce heat insulation. Separate water drainage hose and refrigeration tubes to prevent formation of water droplets.

5.5 Ending of installation

After completion of wrapping and insulation, seal the hole on the wall with a suitable sealant.

5.6 Discharge gas

Place appliance A and then B. Air purging method is as follows:

(1)Turn down the nuts on the wide and narrow tubes.

(2)Loose the nut of the flared wide tube one complete turn with a spanner.

(3)Turn counterclockwise to open the core of the valve with a socket screw wrench. Some gas will come out from under the nut of the flared end of the wide tube. Tighten the nut 10 to 15 seconds later.

(4)Test for leakage at the tube connector with soapy water or a meter. If there is no leakage, turn counterclockwise to open the tube core of the valve on the wide tube with a socket screw wrench.

(5)Tighten the nuts on the wide , narrow tube valves and the valve cover.

Please contact the technical service for further information.

26

Page 29
Image 29
Hisense Group KF-5002GWE REFRIGERANT TUBE 5.1 Flaring the tube, Connection of the tubes, Wrapping the tubes, Discharge gas