3–33

SJ100 Inverter

 

 

“B” Function

Run

 

Defaults

 

 

 

 

 

 

 

 

 

 

 

 

 

Func.

Name /

Description

Mode

–FE

–FU

–FR

Units

 

 

Edit

 

 

Code

SRW Display

(CE)

(UL)

(Jpn)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

B_88

Restart mode after FRS

Selects how the inverter

00

00

00

 

 

 

 

 

resumes operation when the

 

 

 

 

 

 

 

 

RUN FRS

ZST

 

 

 

 

 

 

 

 

free-run stop (FRS) is

 

 

 

 

 

 

 

 

 

 

cancelled, two options:

 

 

 

 

 

 

 

 

 

 

00... Restart from 0Hz

 

 

 

 

 

 

 

 

 

 

01... Restart from frequency

 

 

 

 

 

 

 

 

 

 

detected from real speed of

 

 

 

 

 

 

 

 

 

 

motor (frequency matching)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

B_89

Data select for digital

Select the monitoring data to

01

01

01

 

 

 

operator OPE-J

send to the optional remote

 

 

 

 

 

 

 

 

 

 

hand-held digital operator,

 

 

 

 

 

 

 

 

PANEL

d01

 

 

 

 

 

 

 

 

seven option codes:

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

01... Output frequency (D_01)

 

 

 

 

 

 

 

 

 

 

02... Output current (D_02)

 

 

 

 

 

 

 

 

 

 

03... Motor direction (D_03)

 

 

 

 

 

 

 

 

 

 

04... PID PV feedback (D_04)

 

 

 

 

 

 

 

 

 

 

05... Input states for input

 

 

 

 

 

 

 

 

 

 

terminals (D_05)

 

 

 

 

 

 

 

 

 

 

06... Output states for output

 

 

 

 

 

 

 

 

 

 

terminals (D_06)

 

 

 

 

 

 

Configuring ParametersDrive

 

 

 

07... Scaled output frequency

 

 

 

 

 

 

 

 

 

(D_07)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

B_90

Dynamic braking usage

Selects the rate of use (in %) of

0.0

0.0

0.0

%

 

 

 

ratio

 

the regenerative braking

 

 

 

 

 

 

 

 

 

 

resistor per 100 sec. intervals,

 

 

 

 

 

 

 

 

BRD-%ED

000.0%

 

 

 

 

 

 

 

 

range is 0.0 to 100.0%

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

0% . Dynamic braking disabled

 

 

 

 

 

 

 

 

 

 

>0% Enabled, per value

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

B_91

Stop mode selection

Selects how the inverter stops

00

00

00

 

 

 

 

 

 

the motor, two option codes:

 

 

 

 

 

 

 

 

RUN STP

DEC

 

 

 

 

 

 

 

 

00... DEC (decelerate and stop)

 

 

 

 

 

 

 

 

 

 

01... FRS (free run to stop)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

B_92

Cooling fan control

Selects when the fan is ON per

00

00

00

 

 

 

 

 

inverter operation, two options:

 

 

 

 

 

 

 

 

INIT FAN-CTL OFF

 

 

 

 

 

 

 

 

00... Fan is always ON

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

01... Fan is ON during run,

 

 

 

 

 

 

 

 

 

 

OFF during stop

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

B_90: Dynamic braking usage ratio – This parameter limits the amount of time the inverter can use the dynamic braking accessory device without entering the Trip Mode. Please refer to “Dynamic Braking” on page 5–5 for more information on dynamic braking accessories.