3–12

“A” Group: Standard Functions

 

 

 

 

“A” Function

Run

 

Defaults

 

 

 

 

 

 

 

 

 

 

 

 

 

Func.

Name /

Description

Mode

–FE

–FU

–FR

Units

 

 

Edit

 

 

Code

SRW Display

(CE)

(UL)

(Jpn)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

A_20

Multi-speed frequency

Defines the first speed of a

0

0

0

Hz

 

 

 

setting

 

multi-speed profile, range is

 

 

 

 

 

 

 

 

 

 

0 to 360 Hz

 

 

 

 

 

 

 

 

SPD FS

000.0Hz

 

 

 

 

 

 

 

 

A_20 = Speed 0 (1st motor)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

A220

Multi-speed frequency

Defines the first speed of a

0

0

0

Hz

 

 

 

setting, 2nd motor

multi-speed profile for 2nd

 

 

 

 

 

 

 

 

 

 

motor, range is 0 to 360 Hz

 

 

 

 

 

 

 

 

SPD 2FS

000.0Hz

 

 

 

 

 

 

 

 

A_20 = Speed 0 (2nd motor)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

A_21

Multi-speed frequency

Defines 15 more speeds,

see

see

see

Hz

 

 

to

settings

 

range is 0 to 360 Hz.

 

next

next

next

 

 

 

A_35

(for both motors)

A_21= Speed 1...

 

row

row

row

 

 

 

 

 

 

A_35 = Speed 15

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

SPD 1

000.0Hz

A_21

 

0

0

5

 

 

 

 

SPD 2

000.0Hz

A_22

 

0

0

10

 

 

 

 

SPD 3

000.0Hz

A_23

 

0

0

15

 

 

 

 

SPD 4

000.0Hz

A_24

 

0

0

20

 

 

 

 

SPD 5

000.0Hz

A_25

 

0

0

30

 

 

 

 

 

 

Configuring ParametersDrive

 

 

SPD 6

000.0Hz

A_26

 

0

0

40

 

 

 

SPD 7

000.0Hz

A_27

 

0

0

50

 

 

 

 

 

 

 

 

 

SPD 8

000.0Hz

A_28

 

0

0

60

 

 

 

 

SPD 9

000.0Hz

A_29

 

0

0

0

 

 

 

 

SPD 10

000.0Hz

A_30

 

0

0

0

 

 

 

 

SPD 11

000.0Hz

A_31

 

0

0

0

 

 

 

 

SPD 12

000.0Hz

A_32

 

0

0

0

 

 

 

 

SPD 13

000.0Hz

A_33

 

0

0

0

 

 

 

 

SPD 14

000.0Hz

A_34

 

0

0

0

 

 

 

 

SPD 15

000.0Hz

A_35

 

0

0

0

 

 

 

 

 

 

 

 

 

 

 

 

 

A_38

Jog frequency setting

Defines limited speed for jog,

1.0

1.0

1.0

Hz

 

 

 

 

 

range is 0.5 to 9.99 Hz

 

 

 

 

 

 

 

 

Jogging

01.00Hz

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

A_39

Jog stop mode

Define how end of jog stops

00

00

00

 

 

 

 

 

the motor; three options:

 

 

 

 

 

 

 

 

Jog Mode

0

 

 

 

 

 

 

 

 

00... Free-run stop

 

 

 

 

 

 

 

 

 

 

01... Controlled deceleration

 

 

 

 

 

 

 

 

 

 

02... DC braking to stop