4–23

SJ100 Inverter

Remote Control Up and Down Functions

The [UP] [DWN] terminal functions can adjust the output frequency for remote control while the motor is running. The acceleration time and deceleration time of this function is same as normal operation ACC1 and DEC1 (2ACC1,2DEC1). The input terminals operate according to these principles:

Acceleration - When the [UP] contact is turned ON, the output frequency accelerates from the current value. When it is turned OFF, the output frequency maintains its current value at that moment.

Deceleration - When the [DWN] contact is turned ON, the output frequency deceler- ates from the current value. When it is turned OFF, the output frequency maintains its current value at that moment.

In the graph below, the [UP] and [DWN] terminals activate while the Run command remains ON. The output frequency responds to the [UP] and [DWN] commands.

Output

frequency

1 [UP] 0 1 [DWN] 0

[FW], [RV] 10

 

 

 

 

 

 

 

 

 

 

 

t

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Option

Terminal

Function Name

Input

 

 

 

Description

Code

Symbol

State

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

27

UP

Remote Control

ON

Accelerates (increases output frequency) motor

 

 

UP Function (motor-

 

from current frequency

 

 

ized speed pot.)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

OFF

Output to motor operates normally

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

28

DWN

Remote Control

ON

Decelerates (decreases output frequency) motor

 

 

DOWN Function

 

from current frequency

 

 

(motorized speed

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

OFF

Output to motor operates normally

 

 

pot.)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Valid for inputs:

C_01, C_02, C_03, C_04,

Example (requires input configuration—

 

 

C_05, C_06

 

see page 3–34):

Required settings:

A_01 = 02

 

 

 

 

DWN UP

 

 

 

 

 

 

 

 

 

 

 

 

L

6

5

4

3

2

1

P24

 

Notes:

 

 

 

This feature is available only when the frequency

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

command source is programmed for operator

 

 

 

 

 

 

 

 

 

 

 

 

control. Confirm A_01 is set to 02.

 

 

 

 

 

 

 

 

 

 

 

 

 

This function is not available when [JG] is in use.

The range of output frequency is 0 Hz to the value

in A_04 (maximum frequency setting).

See I/O specs on page 4–6.

 

The minimum ON time of [UP] and [DWN] is 50 ms.

This setting modifies the inverter speed from using F_01 output frequency setting as a starting point.