3–11

SJ100 Inverter

 

 

“A” Function

Run

 

Defaults

 

 

 

 

 

 

 

 

 

 

Func.

Name /

 

Description

Mode

–FE

–FU

–FR

Units

 

Edit

Code

SRW Display

 

(CE)

(UL)

(Jpn)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

A_11

O/OI–L input active

 

The output frequency corre-

0

0

0

Hz

 

range start frequency

 

sponding to the analog input

 

 

 

 

 

 

 

 

 

range starting point

 

 

 

 

 

 

IN EXS

000.0Hz

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

A_12

O/OI–L input active

 

The output frequency corre-

0

0

0

Hz

 

range end frequency

 

sponding to the analog input

 

 

 

 

 

 

 

 

 

range ending point

 

 

 

 

 

 

IN EXE

000.0Hz

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

A_13

O/OI–L input active

 

The starting point (offset) for

0

0

0

%

 

range start voltage

 

the active analog input range

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

IN EX%S

000%

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

A_14

O/OI–L input active

 

The ending point (offset) for

100

100

100

%

 

range end voltage

 

the active analog input range

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

IN EX%E

100%

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

A_15

O/OI–L input start

 

Two options; select codes:

01

01

01

 

frequency enable

 

00... Use offset (A_11 value)

 

 

 

 

 

 

 

 

 

01... Use 0 Hz

 

 

 

 

 

 

IN LEVEL

0Hz

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

A_16

External frequency

 

Range n = 1 to 8, where n =

8

8

8

Sam-

 

filter time constant

 

number of samples for avg.

 

 

 

 

ples

 

 

 

 

 

 

 

 

 

 

 

IN F-SAMP

 

8

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Multi-speed and Jog Frequency Setting

The SJ100 inverter has the capability to store and output up to 16 preset frequencies to the motor (A_20 to A_35). As in traditional motion terminology, we call this multi-speed profile capability. These preset frequencies are selected by means of digital inputs to the inverter. The inverter applies the current acceleration or deceleration setting to change from the current output frequency to the new one. The first multi-speed setting is duplicated for the second motor settings (the remaining 15 multi-speeds apply only to the first motor).

The jog speed setting is used whenever the Jog command is active. The jog speed setting range is arbitrarily limited to 10 Hz, to provide safety during manual operation. The acceleration to the jog frequency is instantaneous, but you can choose from three modes for the best method for stopping the jog operation.

Parameters Drive

Configuring