5–6

Dynamic Braking

Dynamic Braking Usage Ratio

The inverter controls braking via a duty cycle

BRD

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

method (percent of the time braking is ON

 

 

 

 

t1

 

 

 

 

 

 

t2

 

 

 

 

 

 

t3

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

versus total time). Parameter B_90 sets the

ON

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

dynamic braking usage ratio. In the graph to

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

the right, the example shows three uses of

OFF

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

dynamic braking in a 100-second period. The

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

inverter calculates the average percentage

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

(t1 + t2 + t3)

 

 

 

t

usage in that time (T%). The percentage of

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

T% =

100

 

 

 

 

 

B 90

------------------------------

 

 

 

 

usage is proportional to the heat dissipated. If

 

 

 

 

 

 

100 seconds

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

T% is greater than the B_90 parameter setting,

the inverter enters the Trip Mode and turns OFF the frequency output.

Please note the following:

When B_90 is set for 0%, dynamic braking is not performed.

When the T% value exceeds the limit set by B_90, dynamic braking ends.

When mounting an external dynamic braking unit, set the usage ratio (B_90) to 0.0 and remove the external resistors.

The cable from the external resistor to the inverter must not exceed 5 m (16 ft.) length.

The individual wires from the resistor to the inverter must not be bundled together.

Motor Control

Accessories