SJ100 Inverter
The SJ100 inverter has a
•00 = Variable frequency with constant torque
•01 = Variable frequency with reduced torque
•02 = Sensorless vector control (SLV)
NOTE: Although
Most of the “H” Group parameters are dedicated to storing SLV parameters. The inverter comes from the factory with default settings for these parameters. To benefit fully from SLV control, you must use A_44 to select SLV control, and initiate the
WARNING: You may need to disconnect the load from the motor before performing
Follow the steps below to
| Step |
| Parameter | Parameter Setting or Action | Notes |
|
|
|
|
|
|
|
|
| |||
| Code | Name |
| Monitoringand |
| |||
|
|
|
|
|
| |||
|
|
|
|
|
|
|
| |
|
|
|
|
|
|
|
| |
| 1 | F_02 | Acceleration (1) | Set to a time greater than 10 | Parameters F_02 and F_03 must |
| Operations | |
|
|
|
| seconds | be equal in order for the moment |
| ||
|
|
|
|
|
|
| ||
|
|
|
|
| of inertia data to be correct. |
|
|
|
| 2 | F_03 | Deceleration (1) | Set the same as setting F_02 |
|
|
| |
| Increase the time if |
|
|
| ||||
|
|
|
|
|
|
|
| |
|
|
|
|
| or |
|
|
|
|
|
|
|
|
|
|
|
|
| 3 | H_03 | Motor capacity | Varies with inverter (default | Setting is in kW |
|
|
|
|
|
|
| value will be correct) |
|
|
|
|
|
|
|
|
|
|
|
|
|
| 4 | H_04 | Motor poles | Set the poles 2 / 4 / 6 / 8 to | Refer to the motor specifications |
|
|
|
|
|
| setting | match motor | label |
|
|
|
|
|
|
|
|
|
|
|
|
| 5 | A_01 | Frequency source | Set = 02 (selects parameter | The |
|
|
|
|
|
| setting | F_01 as source of output | automatically control the speed |
|
|
|
|
|
|
| frequency) |
|
|
|
|
|
|
|
|
|
|
|
|
|
| 6 | A_03 | Base frequency | Set = 50 or 60 for your motor | Default= 50 (Europe) / 60(US) |
|
|
|
|
|
| setting |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| 7 | A_20 | Set A_20 > 0 | If A_20 = 0, |
|
|
| |
|
|
| frequency setting |
| performed |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|