Honeywell STR12D warranty 3000 210 100 7 30 to

Models: STR12D

1 36
Download 36 pages 39.95 Kb
Page 9
Image 9
3000

34-ST-03-64 Page 9

Performance Under Rated Conditions * - Model STR17G (0-100 to 0-3000 psig)

Parameter

Upper Range Limit **

psig

 

bar

 

 

Minimum Span

psig

 

bar

 

 

Turndown Ratio

 

Zero Elevation and Suppression

Accuracy (Reference – Includes combined effects of linearity, hysteresis, and repeatability)

Accuracy includes residual error after averaging successive readings.

For FOUNDATION Fieldbus use Digital Mode specifications. For HART use Analog Mode specifications.

Description

3000

210

100

7

30 to 1

No limit except minimum span from absolute zero to 100% of URL. Specifications valid over this range.

In Analog Mode: ±0.15% of calibrated span or upper range value (URV), whichever is greater.

For URV below reference point (300 psi), accuracy equals:

 

300 psi

 

21 bar

±0.10 + 0.05 (

 

) or ±0.10 + 0.05

(

 

) in % of span

span psi

span bar

In Digital Mode: ±0.125% of calibrated span or upper range value (URV), whichever is greater.

For URV below reference point (300 psi), accuracy equals:

 

300 psi

 

21 bar

±0.075 + 0.05 (

 

) or

±0.075 + 0.05 (

 

) in % of span

span psi

span bar

*Performance specifications are based on reference conditions of 25°C (77°F), zero (0) static pressure, 10 to 55% RH, and 316L Stainless Steel barrier diaphragm.

**Transmitter URL limit or maximum seal pressure rating, whichever is lower.

Page 9
Image 9
Honeywell STR12D warranty 3000 210 100 7 30 to