3.Setup

3.Setup

1)Secure the legs to the remote condenser unit with the 8 bolts and nuts provided. See Fig. 11.

2)The legs have 8 mounting holes. Secure the legs with 8 bolts (not included).

Fig. 11

4. Line Set

Bolts with Split Lock Washer and Flat Washer

4. Line Seta)Factory Line Set InstallationManual background Nuts

Manual backgroundManual backgroundMounting Holes

CAUTION

The icemaker, line set, and remote condenser unit must contain the same type of refrigerant. Mixing of refrigerants will result in improper operation and possible damage to the refrigeration system.

Precharged factory line sets, available as optional equipment from Hoshizaki America, are recommended. For details, see "II.G.4.a) Factory Line Set Installation." Field fabricated line sets are allowed. For details, see "II.G.4.b) Field Fabricated Line Set Installation."

The maximum line length for the standard refrigerant charge is 66 feet. With additional refrigerant, the maximum line length is 100 feet. For details, see "II.G.5. Refrigerant Charge (Line Set Exceeding 66 Feet)."

a)Factory Line Set Installation

1)Route the factory line set (5/8" OD discharge line and 3/8" OD liquid line) from the remote condenser unit to the icemaker. Leave a service loop behind the icemaker to allow the icemaker to be pulled out for service. See Fig. 12. Factory fabricated line sets are precharged and do not need to be evacuated. If the line set is too long or too short, see "II.G.4.a)(1) Factory Line Set Modification."

Note: The service loop is not considered an oil trap.

CAUTION

1.Ensure that there are no traps and no kinks in the line set.

2.Do not coil extra line set.

2)Connect the refrigerant lines to the appropriate male fittings on the remote condenser unit first and then at the icemaker. Make a proper connection as follows:

a.Remove the protective covers from the male fitting and female coupling.

b.Apply Polyol Ester (POE) refrigerant oil or Parker Super O Lube to the entire male fitting, including O‑ring, diaphragm, and threads before making the connection. See Fig. 13.

CAUTION

Do not use thread sealant on the fittings. Use POE refrigerant oil or Parker Super O Lube only.

c. Make sure the male fitting and female coupling are properly aligned, then start the connection by hand to ensure that it is not cross threaded.

22