2. Water-Cooled Condenser
a) Connection to an Open Drain System
•Condenser water supply inlet is 1/2" female pipe thread (FPT). A minimum of 3/8" nominal
ID copper water tubing or equivalent is required for the condenser water supply line.
•A condenser water supply line
•Condenser drain outlet is 3/8" FPT. A minimum of 3/8" nominal ID hard pipe or equivalent is required for the condenser drain line.
•In some areas, a back flow preventer may be required in the cooling water circuit.
•In order to maintain the proper high side pressure, the condenser water supply inlet temperature should not drop below 45°F (7°C) and the condenser drain outlet temperature must be in the 104°F to 115°F (40°C to 46°C) range. Once the icemaker installation
is complete, confirm the condenser drain outlet temperature 5 minutes after a freeze cycle starts. If the condenser drain outlet temperature is not in the proper range, use a flat blade screwdriver to rotate the adjustment screw on the water‑regulating valve until the temperature is in the proper range (rotate counterclockwise to raise temperature or clockwise to lower temperature).
| Icemaker Water Supply | Icemaker Water Supply Inlet 1/2" FPT | |
Minimum 3/8" Nominal | Line | ||
| |||
|
| ||
ID Copper Water Tubing |
|
|
Icemaker Water Supply Line Drain Valve
Condenser Water Supply Inlet 1/2" FPT
Vent Tube
Condenser Drain Outlet 3/8" FPT
Minimum 3/8" Nominal
ID Copper Water Tubing
Condenser Water Supply Line
Condenser Water Supply Line Drain Valve
Minimum 3/8" Nominal ID Hard Pipe
Separate piping to approved drain. Leave a 2 inch (5 cm) vertical air gap between the end of each pipe and the drain.
Vent Tube
Icemaker
Bin
Icemaker
Drain Outlet
3/4" FPT
Condensation
Drain Outlet
3/8" OD Hard
Tube
|
| |
air gap |
| Bin Drain Outlet |
| Minimum 3/4" | 3/4" FPT |
| Nominal ID Hard Pipe |
|
Floor |
|
|
Drain |
| |
Connection To An Open Drain System |
Fig. 18
29