•On single phase models, the white lead must be connected to the neutral conductor of the power source. CAUTION! Miswiring may result in severe damage to the icemaker. See Fig. 8a.
•On three phase models, the transformer’s voltage tap switch must be positioned to match incoming voltage at startup. See Fig. 8b.
•CAUTION! On three phase models, connect the highest incoming voltage supply ("stinger leg") to the red power supply wire (red common wire to the compressor).
•The opening for the power supply connection is 7/8" DIA to fit a 1/2" trade size conduit.