Hoshizaki KM-2400SRF3, KM-2400SRH3 service manual 2nd Cycle and after with no pump drain

Models: KM-2400SRF3 KM-2400SRH3

1 50
Download 50 pages 8.4 Kb
Page 16
Image 16
2nd Cycle and after with no pump drain

2nd Cycle and after with no pump drain

IMPORTANT

Freeze cycle time is limited to 50 minutes even if Float Switch does not open.

1.Float Switch opens and signals to complete freeze cycle.

2.Thermistor reads 48° F. Defrost Timer starts counting.

IMPORTANT Water Valve opening is limited to 6 minutes.

4.After the first 5 minutes in freeze cycle. Ready to complete freeze cycle when Float Switch circuit opens.

IMPORTANT

Board never accepts freeze completion signal within the first 5 minutes in freeze cycle.

3.Defrost Timer stops counting.

Defrost cycle is completed and freeze cycle starts.

IMPORTANT

1.Board never accepts defrost completion signal within the first 2 minutes in defrost cycle.

2.Defrost cycle time is limited to 20 minutes even if Defrost Timer does not stop counting.

16

Page 16
Image 16
Hoshizaki KM-2400SRF3 2nd Cycle and after with no pump drain, IMPORTANT Water Valve opening is limited to 6 minutes