2nd Cycle and after with pump drain
IMPORTANT
Freeze cycle time is limited to 50 minutes even if Float Switch does not open.
1.Float Switch opens and signals to complete freeze cycle.
Drain timer starts counting.
2.Drain timer stops counting. Pump drain is completed
3.Thermistor reads 48° F. Defrost Timer starts counting.
5.After the first 5 minutes in freeze cycle. Ready to complete freeze cycle when Float Switch circuit opens.
IMPORTANT
Board never accepts freeze completion signal within the first 5 minutes in freeze cycle.
IMPORTANT Water Valve opening is limited to 6 minutes.
4.Defrost Timer stops counting.
Defrost cycle is completed and freeze cycle starts.
IMPORTANT
1.Board never accepts defrost completion signal within the first 2 minutes in defrost cycle.
2.Defrost cycle time is limited to 20 minutes even if Defrost Timer does not stop counting.
15