6)A liquid charge is recommended for charging an
7)Allow the system to charge with liquid until the proper charge weight is met.
8)If necessary, add any remaining charge to the system through the
9)Close the two refrigerant access valves, and disconnect the service manifold hoses.
10)Cap the access valves to prevent a possible leak.
B.Brazing
DANGER
1.Refrigerant
2.Refrigerant
3.Always recover the refrigerant and store it in an approved container. Do not discharge the refrigerant into the atmosphere.
4.Do not use silver alloy or copper alloy containing arsenic.
5.Do not use
Note: Because the pipes in the evaporator case are specially coated to resist corrosion, it is important to make connections outside the evaporator case when possible. If it is necessary to braxe inside the evaporator case, use sandpaper to remove the coating from the brazing connections before unbrazing the components.
C. Removal and Replacement of Compressor
IMPORTANT
Always install a new drier every time the sealed refrigeration system is opened. Do not replace the drier until after all other repair or replacement has been made.
Note: When replacing a compressor with a defective winding, be sure to install the new start capacitor and start relay supplied with the replacement compressor. Due to the ability of the POE oil in the compressor to absorb moisture quickly, the compressor must not be opened more than 15 minutes for replacement or service. Do not mix lubricants of different compressors even if both are charged with
1) Turn off the power supply.
40