available in the load leads for prolonged operation into a 5 A load during ac low line at high ambient temperature conditions.

There is a similar stipulation for 80 W low voltage outputs at l0 A under the same conditions as above. See Figure 4-2A for worst case voltages available at the output terminals.

Table 4-1. Stranded Copper Wire Ampacity and Maximum Wire Lengths to Limit Load Lead Voltage

Drop

 

Ampacity Per Wire (Amps)

Resistivity

Max Length to Limit

 

 

 

 

Voltage to 1 V Per Lead

Wire Size

2 Wire Bundled

4 Wire Bundled

 

5 A

10 A

20 A

(AWG)

 

 

(Ω /ft)

 

(feet)

 

20

7.8

6.9

0.0102

20

10

5

18

14.5

12.8

0.0064

30

15

7.5

16

18.2

16.1

0.0040

50

25

12.5

14

29.3

25.9

0.0025

--

40

20

12

37.6

33.2

0.0016

--

--

30

(Cross Section

 

 

(Ω /m)

 

(meters)

 

Area in mm2)

 

 

 

 

 

 

0.5

7.8

6.9

0.0401

5

2.4

1.2

0.75

9.4

8.3

0.0267

7.4

3.8

1.8

1

12.7

11.2

0.0200

10

5

2.6

1.5

15.0

13.3

0.0137

14.6

7.2

3.6

2.5

23.5

20.8

0.0082

--

12.2

6

Notes:

1.Ampacities for AWG wires are derived from MIL-W-5088B. Maximum ambient temp: 55°C. Maximum wire temp: 105°C.

2.Ampacities for metric wires are derived from IE Publication 335-1.

3.Ampacity of aluminum wire is approximately 84% of that listed for copper wire.

4.Because of wire inductance considerations, it is recommended that you keep your load leads twisted, tie wrapped, or bundled together and less than 50 feet (14.7 meters) in length per lead.

5.See pages 47 & 48 for information on wire gauge considerations with capacitive loads.

NOTE

To prevent tripping of the overvoltage circuit, pick a wire size sufficient to handle the FULL output

 

current of the unit no matter what the intended load current or current limit setting.

Table 4-1 lists the resistivity for various wire sizes and the maximum lengths to limit the voltage drop to 1.0 volts for various currents.

NOTE

The OVP circuit senses at the main output terminals and not on the sense leads. Thus, the voltage

 

sensed by the OVP circuit could be as much as 2 V higher than the voltage being regulated at the load.

 

Program the OVP trip voltage accordingly when using remote sensing. In addition, if the voltage drop

 

exceeds 1.5 V on either load lead, a protective circuit will fire the OVP circuit regardless of the OVP

 

setting.

Load lead resistance is an important factor relating to the CV stability of the supply with remote sensing of capacitive loads. If high capacitance loads are expected, you should not use wire gauges heavier than 12 to 14 AWG for long runs of load lead. See Figure 1-4 for more information about stability with output capacitors.

48 Output Connections and Operating Information

Page 48
Image 48
HP 6623A, 6624A, 6621A manual Wire Bundled 10 a 20 a, Feet, Cross Section Meters Area in mm2

6624A, 6621A, 6623A specifications

The HP 6623A, 6621A, and 6624A are precision DC power supplies widely recognized for their reliability and performance in various laboratory and industrial applications. These models are part of HP's 662X series, designed to cater to the needs of engineers, researchers, and technicians who require accurate power sources for their testing and development activities.

The main features of the HP 6623A, 6621A, and 6624A include their high stability, low ripple, and excellent load regulation, ensuring that the output voltage and current remain stable during testing. The power supplies provide multiple output channels, allowing users to power multiple devices simultaneously. The flexibility in setting voltage and current levels makes these models ideal for a wide range of applications, including semiconductor testing, device characterization, and system integration.

One of the standout technologies in the HP 662X series is the use of smart design techniques that minimize noise and enhance output performance. These power supplies incorporate advanced feedback mechanisms to maintain steady output, even under varying load conditions. Additionally, they feature programmable outputs, which means users can adjust the output levels through a connected computer or control system, streamlining the testing process and improving efficiency.

The HP 6623A model offers three independent outputs, with total power capabilities of 40 watts. It includes a 0-20V output, which can deliver up to 2A of current, along with two additional outputs that are adjustable. The 6621A provides a single output option, delivering a maximum of 20V and 2A, making it well-suited for simple applications where a single power source is required. In contrast, the HP 6624A stands out with its four independent output channels, providing a total of 60 watts, making it the most versatile of the three models.

Characteristics of these power supplies include user-friendly interfaces, allowing for easy configuration and monitoring of settings. LED indicators provide real-time feedback on voltage and current levels, enabling users to quickly assess the performance of their tests. Moreover, built-in protection features safeguard both the power supply and the connected devices from overvoltage and overcurrent conditions.

Overall, the HP 6623A, 6621A, and 6624A power supplies embody advanced engineering and design, making them invaluable tools for professionals looking for high-quality, reliable power sources for their electronic testing needs.