Off

On

Off

On—Batt

On—Batt

On—Batt

On—Batt

Off

UPS is on battery (on page

 

 

 

ery

ery

ery

ery

 

58)—No utility power

 

 

 

capacity

capacity

capacity

capacity

 

 

 

 

 

<25%

>25%

>50%

>75%

 

 

 

 

 

 

 

 

 

 

 

*

*

*

Off

*

*

Flashing

*

Overtemperature condition (on

 

 

 

 

 

 

 

 

page 59)

Off

Off

On

Flashing

Flashing

Flashing

Flashing

Flashing

Internal UPS fault condition (on

 

 

 

 

 

 

 

 

page 59)

Flashing

Off

Off

Flashing

Flashing

Flashing

Flashing

Flashing

REPO condition (on page 59)

 

 

 

 

 

 

 

 

 

*

Off

*

Off

*

Flashing

*

*

Site wiring condition (on page

 

 

 

 

 

 

 

 

59)

 

 

 

 

 

 

 

 

 

*

Off

*

On

On

On

On

Flashing

Overload condition (on page

 

 

 

 

 

 

 

 

59)—UPS power capacity is

 

 

 

 

 

 

 

 

exceeded with no other faults

 

 

 

 

 

 

 

 

 

*

Off

*

Off

*

*

*

Flashing

Overload condition (on page

 

 

 

 

 

 

 

 

59)—UPS power capacity is

 

 

 

 

 

 

 

 

exceeded while other faults

 

 

 

 

 

 

 

 

exist

 

 

 

 

 

 

 

 

 

Off

On

Off

On—Batt

On—Batt

On—Batt

On—Batt

Flashing

Overload condition (on page

 

 

 

ery

ery

ery

ery

 

59)—UPS power capacity is

 

 

 

capacity

capacity

capacity

capacity

 

exceeded while on battery with

 

 

 

<25%

>25%

>50%

>75%

 

no other faults

 

 

 

 

 

 

 

 

 

Off

On

Off

Off

Off

Off

Flashing

Flashing

Overload condition (on page

 

 

 

 

 

 

 

 

59)—UPS power capacity is

 

 

 

 

 

 

 

 

exceeded while on battery with

 

 

 

 

 

 

 

 

overtemperature fault

 

 

 

 

 

 

 

 

 

Off

Flashing

Off

Flashing

Flashing

Flashing

Flashing

Flashing

Unit is powering down

 

 

 

 

 

 

 

 

 

Flashing

Flashing

Flashing

Flashing

Flashing

Flashing

Flashing

Flashing

Checksum failure error (on

 

 

 

 

 

 

 

 

page 60)

* This LED can be in any state.

For the location of individual LEDs, see "UPS front panel LED indicators (on page 8)."

UPS is in Auto-Bypass mode

The UPS transfers from Operate mode (on page 40) to Auto-Bypass when one of the following fault conditions is detected:

Inverter AC over voltage

Inverter AC under voltage

Rectifier input over current

Inverter output over current

Inverter fault

Heat sink over temperature

Fan failure

Overload

The load is supported, but not protected while in Auto-Bypass mode.

Troubleshooting 56