UPS model

Load segment

Output receptacles

 

 

 

1 x L6-20R

2

3 x IEC-320-C13

1 x IEC-320-C19

R/T3000 INTL

1

3 x IEC-320-C13

1 x IEC-320-C19

2

3 x IEC-320-C13

1 x IEC-320-C19

Power protection specifications

UPS model

VA

Nominal power

Nominal voltage setting

 

 

rating (W)

 

 

 

 

 

R/T3000 NA/JPN

2880 /

2700 / 2250

120/100

 

2400

 

 

R/T3000h

3300

3000

204

NA/JPN

 

 

 

R/T3000 INTL

3300

3000

230

Output tolerance specifications

Source of power

Regulation

 

 

Utility power (nominal

-10% to +6% of nominal output voltage rating

range)

(within the guidelines of the Computer Business

 

Equipment Manufacturers Association)

 

 

Battery power

±5% of nominal output voltage rating

Output feature specifications

Feature

Specification

 

 

Online efficiency

94% nominal input voltage

Voltage wave shape

Sine wave; 5% THD with typical PFC load

Surge suppression

300J via MOVs

Noise filtering

EN 55022 line filter for normal and common mode

 

use

 

 

Battery specifications

Feature

Specification

 

 

Type

12 V, 5 AH, sealed, maintenance-free, rechargeable, valve

 

regulated lead-acid batteries with a 3-5 year service life at 25°C

 

(77°F).

 

 

Voltage

The battery modules have a battery string voltage of 120 V.

 

 

Specifications 62