•Avoid allowing the wires to hang in the rear of the UPS.
•Use tie wraps and tie wrap blocks to secure the wires tightly to the rack and the rear of the UPS.
For more information about the REPO port, see "REPO port (on page 11)".
For information about verifying the REPO connection, see "Verifying the REPO port connection (on page 44)".
Connecting the ground bonding cable
NOTE: UPS appearance might vary depending on the specific unit installed.
The ground bonding screw is provided as an attachment point for conductors. Use a ground bonding cable if the rack contains any conductors for the purpose of functional grounding or bonding of ungrounded metal parts.