Invacare 3800, 3750 Electrical Installation, NOTE For this procedure, refer to .6 on page, Danger

Models: 3750 3800

1 36
Download 36 pages 1.41 Kb
Page 18
Image 18
Electrical Installation

SECTION 2—PARTS AND INSTALLATION

Electrical Installation

DANGER

When using electrical products, basic precautions should always be followed, including the following:

RISK OF ELECTRIC SHOCK. Connect the bathtub only to a circuit protected by a ground-fault circuit-interrupter (GFCI). Use a 15 AMP GFCI breaker only.

The National Electric Code requires the use of a ground fault circuit interrupter on all therapeutic pools and tubs (hydrotherapeutic tanks). Failure to follow this requirement could result in serious or fatal injury.

Grounding is required. The ground wire MUST be continuous from the motor to the GFCI service panel.

ELECTRICAL SHOCK HAZARD. All disassembly and maintenance of the tub MUST be done by a qualified technician, certified electrician or plumber. Be certain all electrical work is in compliance with local electrical codes.

All electrical connections are to be water resistant.

Disconnect electrical supply or turn off the circuit breaker before performing any maintenance to the tub to avoid electrical shock.

WARNING

All electrical conduit, fittings and wire to unit are to be supplied and installed by a professional electrician in accordance with the National electrical code as a minimum requirement, including the supply and installation of a Ground Fault Circuit Interrupter (GFCI).

For Canadian installation, ground fault interrupter and a 30-minute maximum timer MUST be installed in the electrical circuit. (parts not supplied by ICCG). The unit must be operated through the circuit. The 30-minute timer must be located in a position where a person in the unit cannot reach the timer.

NOTE: For this procedure, refer to FIGURE 2.6 on page 19.

NOTE: Use 15 AMP GFCI breaker only.

1.Ensure a 15 AMP GFCI breaker is installed to protect the unit.

2.Connect the green terminal to the grounding terminal of the electric service supply panel using a continuous green insulated copper wire equivalent in size to the circuit conductors supplying this equipment, but no smaller than No. 8AWG (3.3 mm).

NOTE: The green terminal may be a wire connector marked “G”, “GR”, “Ground” or “Grounding”.

3.Use the pressure wire connector on the exterior of the terminal box to connect the No. 8AWG (8.4 mm) solid copper bonding conductor between the unit and all other electrical equipment and exposed metal in the vicinity, to comply with local requirements.

4.Use a pneumatic air switch with the push button located on the tub deck for On/Off switching.

5.Install a 115 V electrical hook‐up per local electrical codes through a dedicated GFCI circuit.

Recessed Side Entry Bath Tubs

18

Part No 1150695

Page 18
Image 18
Invacare 3800 Electrical Installation, NOTE For this procedure, refer to .6 on page, NOTE Use 15 AMP GFCI breaker only