TABLE 12: GASE RATE - CUBIC FEET PER HOUR1
SECONDS | SIZE OF TEST DIAL | |
FOR ONE |
|
|
REV. | 1/2 CU. FT. | 1 CU. FT. |
|
|
|
10 | 180 | 360 |
12 | 150 | 300 |
14 | 129 | 257 |
16 | 113 | 225 |
18 | 100 | 200 |
|
|
|
20 | 90 | 180 |
22 | 82 | 164 |
24 | 75 | 150 |
26 | 69 | 138 |
28 | 64 | 129 |
|
|
|
30 | 60 | 120 |
32 | 56 | 113 |
34 | 53 | 106 |
36 | 50 | 100 |
38 | 47 | 95 |
|
|
|
40 | 45 | 90 |
42 | 43 | 86 |
44 | 41 | 82 |
46 | 39 | 78 |
48 | 37 | 75 |
|
|
|
50 | 36 | 72 |
52 | 35 | 69 |
54 | 34 | 67 |
56 | 32 | 64 |
58 | 31 | 62 |
60 | 30 | 60 |
|
|
|
1.EXAMPLE: By actual measurement, it takes 38 seconds for the hand on the
CHECKING SUPPLY AIR CFM
To check the supply air CFM after the initial balancing has been completed:
1.Remove the two ¼ inch dot plugs in the duct panel.
2.Insert at least 8 inches of ¼ inch tubing into each of these holes for sufficient penetration into the airflow on both sides of the indoor coil.
3.Using an inclined manometer, determine the pressure drop across the dry evaporator coil. Since the moisture on an evaporator coil may vary greatly, measuring the pressure drop across a wet coil under field conditions would be inaccurate. To ensure a dry coil, the compres- sors should be deactivated while the test is being run.
4.Knowing the pressure drop across a dry coil, the actual CFM through the unit can be determined from the curve in Coil Delta P vs. Supply Air CFM figure.
Failure to properly adjust the total system air quan- tity can result in extensive system damage.
After readings have been obtained, remove the tubes and reinstall the two ¼ inch plugs removed in Step 1.
18 | Johnson Controls Unitary Products |