TABLE 14: SUPERHEAT CHARGING TABLE FOR DYA042
OUTDOOR |
|
| SUPERHEAT AT COMPRESSOR SUCTION (F), AIRFLOW = 400 CFM |
|
| ||||||
|
|
|
| INDOOR WB TEMP. (°F) |
|
|
|
| |||
TEMP. °F |
|
|
|
|
|
|
|
| |||
| 55 | 57 | 59 | 61 | 63 | 65 | 67 | 69 | 71 | 73 | 75 |
65 | 18.0 | 19.7 | 21.4 | 23.0 | 24.7 | 26.3 | 28.0 | 29.1 | 30.2 | 31.3 | 32.4 |
70 | 13.4 | 15.3 | 17.3 | 19.3 | 21.2 | 23.2 | 25.2 | 26.6 | 28.1 | 29.6 | 31.1 |
75 | 8.7 | 10.9 | 13.2 | 15.5 | 17.8 | 20.0 | 22.3 | 24.2 | 26.1 | 28.0 | 29.9 |
80 | - | 6.6 | 9.1 | 11.7 | 14.3 | 16.9 | 19.5 | 21.7 | 24.0 | 26.3 | 28.6 |
85 | - | - | 5.1 | 7.9 | 10.8 | 13.7 | 16.6 | 19.3 | 21.9 | 24.6 | 27.3 |
90 | - | - | - | 6.7 | 9.3 | 11.9 | 14.6 | 17.4 | 20.2 | 23.1 | 25.9 |
95 | - | - | - | 5.5 | 7.8 | 10.2 | 12.5 | 15.5 | 18.5 | 21.5 | 24.5 |
100 | - | - | - | - | 6.3 | 8.0 | 9.8 | 12.9 | 16.1 | 19.2 | 22.4 |
105 | - | - | - | - | - | 5.9 | 7.1 | 10.3 | 13.7 | 16.9 | 20.3 |
110 | - | - | - | - | - | - | - | 7.8 | 11.2 | 14.7 | 18.1 |
115 | - | - | - | - | - | - | - | 5.2 | 8.8 | 12.4 | 16.0 |
TABLE 15: SUPERHEAT CHARGING TABLE FOR DYA048
OUTDOOR |
|
| SUPERHEAT AT COMPRESSOR SUCTION (F), AIRFLOW = 400 CFM |
|
| ||||||
|
|
|
| INDOOR WB TEMP. (°F) |
|
|
|
| |||
TEMP. °F |
|
|
|
|
|
|
|
| |||
| 55 | 57 | 59 | 61 | 63 | 65 | 67 | 69 | 71 | 73 | 75 |
65 | 20.9 | 21.8 | 22.7 | 23.6 | 24.4 | 25.3 | 26.2 | 27.4 | 28.6 | 29.8 | 31.0 |
70 | 17.6 | 18.7 | 19.7 | 20.7 | 21.7 | 22.7 | 23.7 | 25.2 | 26.6 | 28.1 | 29.6 |
75 | 14.4 | 15.5 | 16.6 | 17.8 | 18.9 | 20.0 | 21.2 | 22.9 | 24.7 | 26.4 | 28.2 |
80 | 11.1 | 12.4 | 13.6 | 14.9 | 16.1 | 17.4 | 18.6 | 20.7 | 22.7 | 24.8 | 26.8 |
85 | 7.8 | 9.2 | 10.6 | 12.0 | 13.3 | 14.7 | 16.1 | 18.4 | 20.8 | 23.1 | 25.4 |
90 | 5.8 | 7.0 | 8.2 | 9.3 | 10.5 | 11.7 | 12.9 | 15.7 | 18.6 | 21.5 | 24.4 |
95 | - | - | 5.8 | 6.7 | 7.7 | 8.6 | 9.6 | 13.0 | 16.5 | 19.9 | 23.3 |
100 | - | - | 5.4 | 6.0 | 6.7 | 7.4 | 8.0 | 11.6 | 15.2 | 18.7 | 22.3 |
105 | - | - | - | 5.3 | 5.7 | 6.1 | 6.5 | 10.2 | 13.9 | 17.6 | 21.3 |
110 | - | - | - | - | - | - | - | 8.7 | 12.6 | 16.4 | 20.3 |
115 | - | - | - | - | - | - | - | 7.3 | 11.3 | 15.3 | 19.3 |
TABLE 16: SUPERHEAT CHARGING TABLE FOR DYA060
OUTDOOR |
|
| SUPERHEAT AT COMPRESSOR SUCTION (F), AIRFLOW = 400 CFM |
|
| ||||||
|
|
|
| INDOOR WB TEMP. (°F) |
|
|
|
| |||
TEMP. °F |
|
|
|
|
|
|
|
| |||
| 55 | 57 | 59 | 61 | 63 | 65 | 67 | 69 | 71 | 73 | 75 |
65 | 7.0 | 9.2 | 11.4 | 13.6 | 15.9 | 18.1 | 20.3 | 21.8 | 23.2 | 24.7 | 26.1 |
70 | 6.1 | 8.4 | 10.7 | 13.0 | 15.2 | 17.5 | 19.8 | 21.2 | 22.7 | 24.1 | 25.6 |
75 | 5.3 | 7.6 | 9.9 | 12.3 | 14.6 | 16.9 | 19.3 | 20.7 | 22.2 | 23.6 | 25.0 |
80 | - | 6.8 | 9.2 | 11.6 | 14.0 | 16.3 | 18.7 | 20.2 | 21.6 | 23.1 | 24.5 |
85 | - | 6.0 | 8.4 | 10.9 | 13.3 | 15.8 | 18.2 | 19.6 | 21.1 | 22.5 | 23.9 |
90 | - | - | 6.5 | 8.7 | 10.8 | 12.9 | 15.1 | 17.1 | 19.1 | 21.1 | 23.1 |
95 | - | - | - | 6.5 | 8.3 | 10.1 | 11.9 | 14.5 | 17.1 | 19.7 | 22.3 |
100 | - | - | - | 5.9 | 7.3 | 8.6 | 10.0 | 12.9 | 15.8 | 18.7 | 21.6 |
105 | - | - | - | 5.3 | 6.2 | 7.1 | 8.0 | 11.3 | 14.5 | 17.7 | 20.9 |
110 | - | - | - | - | 5.2 | 5.6 | 6.1 | 9.6 | 13.2 | 16.7 | 20.2 |
115 | - | - | - | - | - | - | - | 8.0 | 11.8 | 15.7 | 19.6 |
20 | Johnson Controls Unitary Products |