Johnson Controls GG9S'MP, TG9S'MP UIM-H-0712, Vent System, Vent Applications And Termination

Models: GG9S'MP TG9S'MP

1 40
Download 40 pages 49.32 Kb
Page 25
Image 25
VENT SYSTEM

364861-UIM-H-0712

VENT SYSTEM

This furnace is certified to be installed with one of two possible vent configurations.

1.Horizontal vent system. This vent system can be installed com- pletely horizontal or combinations of horizontal, vertical, or offset using elbows.

2.Vertical vent system. This vent system can be installed completely vertical or a combination of horizontal, vertical, or offset using elbows.

NOTICE

On 130K BTU models, there is no provision for the vent to exit the top of the cabinet, the vent must always exit one of the sides.

VENT APPLICATIONS AND TERMINATION

When selecting the location for a combustion air / vent termination, the

Maintain 12” minimum clearance above highest anticipated snow level.

12” vertical separation

 

between combustion air

12” minimum

intake and vent.

below overhang

 

 

12” minimum

 

separation between

 

bottom of

 

combustion air pipe

 

and bottom of vent.

 

Maintain 12”

 

minimum clearance

 

above highest

 

anticipated snow

 

level or grade,

 

whichever is higher.

following should be considered:

FIGURE 32: Termination Configuration - 2 Pipe

1.Observe all clearances listed in vent clearances in these instruc- tions.

2.Termination should be positioned where vent vapors will not dam- age plants or shrubs or air conditioning equipment.

3.Termination should be located where it will not be affected by wind gusts, light snow, airborne leaves or allow recirculation of flue gases.

4.Termination should be located where it will not be damaged or exposed to flying stones, balls, etc.

5.Termination should be positioned where vent vapors are not objec- tionable.

6.Horizontal portions of the vent system must slope upwards and be supported to prevent sagging.

7.Direct vent systems must be installed so the vent and the combus- tion air pipes terminate in the same atmospheric zone. Refer to Fig- ures 32 or 33.

12” MIN.

12” MIN.VENT APPLICATIONS AND TERMINATION

12” Minimum below overhang

12” Minimum separation between bottom of combustion air intake and bottom of vent

VENTING MULTIPLE UNITS Maintain 12” minimumclearance above highest anticipated snow level or grade, whichever is higher

Maintain 12” minimum clearance above highest anticipated snow level. Maximum 24” above roof.

12” Min.

12” Min.

FIGURE 31: Termination Configuration - 1 Pipe

FIGURE 33: Termination Configuration - 2 Pipe Basement

VENTING MULTIPLE UNITS

Multiple units can be installed in a space or structure as either a single pipe configuration or a two-pipe configuration.

The combustion air side of the single pipe configuration shown in Figure 31 is referred to in these instructions as ambient combustion air supply. Follow the instructions for ambient combustion air installations, paying particular attention to the section on air source from inside the building. The vent for a single pipe system must be installed as specified in the venting section of these instructions with the vent terminating as shown in Figure 31. Each furnace must have a separate vent pipe. Under NO circumstances can the two vent pipes be tied together.

The combustion air side of the two-pipe configuration shown in Figure 32 can be installed so the combustion air pipe terminates as described in outdoor combustion air or ventilated combustion air sections in these instructions. Follow the instructions for outdoor combustion air or venti- lated combustion air and the instructions for installing the vent system with the vent terminating as shown in Figures 34 or 35. The two-pipe system must have a separate combustion air pipe and a separate vent pipe for each furnace. Under NO circumstances can the two combus- tion air or vent pipes be tied together. The combustion air and vent pipes must terminate in the same atmospheric zone.

Johnson Controls Unitary Products

25

Page 25
Image 25
Johnson Controls GG9S'MP, TG9S'MP UIM-H-0712, Vent System, Vent Applications And Termination, Venting Multiple Units

FAQ

What are the possible vent configurations for the furnace?

The furnace can be installed with a horizontal vent system or a vertical vent system, allowing for various combinations of horizontal, vertical, or offset configurations using elbows.

What are the clearance requirements for the combustion air / vent termination?

Maintain a 12 minimum clearance above the highest anticipated snow level and a 12 minimum separation between the combustion air intake and the vent below overhang.

Can multiple units be installed with a single vent pipe?

Multiple units can be installed in a space or structure as either a single pipe configuration or a two-pipe configuration, with specific instructions for each type.