Table 6: Ratings & Physical / Electrical Data |
|
|
|
|
|
|
|
|
|
| |||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| |||
Input | Output | Nominal | AFUE | Air Temp. Rise | Max. Outlet | Blower | Blower | Max | Total Unit | Min. wire Size | |||||||
|
|
|
| Airflow | % |
|
| Air Temp |
|
| Size | Amps | (awg) @ 75 ft | ||||
MBH | kW | MBH | kW | CFM | m3/min | °F | °C | °F | °C | HP | Amps | Protect | one way | ||||
|
|
| |||||||||||||||
40 | 11.7 | 38 | 11.1 | 800 | 22.7 | 95.5 | 160 | 71.1 | 1/3 | 4.8 | 11x8 | 15 | 8.0 | 14 | |||
60 | 17.6 | 57 | 16.7 | 1000 | 28.3 | 95.5 | 160 | 71.1 | 1/2 | 7.07 | 11x8 | 15 | 10.0 | 14 | |||
60 | 17.6 | 57 | 16.7 | 1200 | 34.0 | 95.5 | 160 | 71.1 | 1/2 | 7.07 | 11x8 | 15 | 10.0 | 14 | |||
80 | 23.4 | 76 | 22.3 | 1200 | 34.0 | 95.5 | 165 | 73.9 | 1/2 | 7.07 | 11x8 | 15 | 10.0 | 14 | |||
80 | 23.4 | 76 | 22.3 | 1600 | 45.3 | 95.5 | 165 | 73.9 | 3/4 | 8.8 | 11x10 | 15 | 11.5 | 14 | |||
80 | 23.4 | 76 | 22.3 | 2200 | 62.3 | 95.5 | 165 | 73.9 | 1 | 14.5 | 11x11 | 20 | 17.0 | 12 | |||
100 | 29.3 | 95 | 27.8 | 1600 | 45.3 | 95.5 | 165 | 73.9 | 3/4 | 8.8 | 11x10 | 15 | 11.5 | 14 | |||
100 | 29.3 | 95 | 27.8 | 2000 | 56.6 | 95.5 | 165 | 73.9 | 1 | 14.5 | 11x11 | 20 | 17.0 | 12 | |||
120 | 35.1 | 114 | 33.4 | 1600 | 45.3 | 95.5 | 170 | 76.7 | 3/4 | 8.8 | 11x10 | 15 | 11.5 | 14 | |||
120 | 35.1 | 114 | 33.4 | 2000 | 56.6 | 95.5 | 165 | 73.9 | 1 | 14.5 | 11x11 | 20 | 17.0 | 12 | |||
130 | 38.1 | 123.5 | 36.2 | 2000 | 56.6 | 95.5 | 175 | 79.4 | 1 | 14.5 | 11x11 | 20 | 17.0 | 12 |
Annual Fuel Utilization Efficiency (AFUE) numbers are determined in accordance with DOE Test procedures.
Wire size and over current protection must comply with the National Electrical Code
SUPPLY VOLTAGE CONNECTIONS
Junction
Box
Connect ground lead to screw
Electrical Entry
Neutral WHT
FIGURE 17: Electrical Wiring
1.Provide a power supply separate from all other circuits. Install over- current protection and disconnect switch per local/national electrical codes. The switch should be close to the unit for convenience in servicing. With the disconnect or fused switch in the OFF position, check all wiring against the unit wiring label. Refer to the wiring dia- gram in this instruction.
2.Remove the wiring box cover screws. Route all power wiring through a conduit connector or other proper bushing that has been installed into the unit opening and the junction box. In the junction box there is a black wire, a white wire and a green ground screw. Connect the power supply as shown on the unit’s wiring label on the inside of the blower compartment door or the wiring schematic in this section. Connect the black wire to L1 (hot) from the power supply. Connect the white wired to neutral. Connect the ground wire
3.The furnace's control system requires correct polarity of the power supply and a proper ground connection. Refer to Figure 17.
The power connection leads and wiring box may be relocated to the left side of the furnace. Remove the screws and cut wire tie holding excess wiring. Reposition on the left side of the furnace and fasten using holes provided.
LOW VOLTAGE CONTROL WIRING CONNECTIONS
Install the
Set the heat anticipator in the room thermostat to 0.4 amps. Setting it lower will cause short cycles. Setting it higher will cause the room temperature to exceed the set points.
Some electronic thermostats do not have adjustable heat anticipa- tors. They should be set to six cycles per hour. Follow the thermostat manufacturer's instructions.
The
12 | Johnson Controls Unitary Products |