Johnson Controls TG9S'MP, GG9S'MP installation manual UIM-H-0712, Bottom Airflow Data SCFM

Models: GG9S'MP TG9S'MP

1 40
Download 40 pages 49.32 Kb
Page 34
Image 34
Bottom Airflow Data (SCFM)

364861-UIM-H-0712

Table 17: Blower Performance CFM - Any Position (without filter) - Bottom Return

Models

 

 

 

 

Bottom Airflow Data (SCFM)

 

 

 

Speed

 

 

 

 

 

 

 

 

 

 

 

 

 

Ext. Static Pressure (in. H2O)

 

 

 

Input/Airflow/Cabinet

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

0.1

0.2

0.3

0.4

0.5

0.6

0.7

0.8

0.9

1.0

 

 

 

 

 

 

 

 

 

 

 

 

 

High

1128

1077

1035

996

950

891

842

781

708

646

40/800/A

Medium High

934

909

867

834

818

780

745

696

631

584

Medium Low

746

735

714

679

653

629

596

585

547

494

 

 

Low

676

652

627

601

581

542

516

474

441

383

 

High

1360

1290

1230

1165

1103

1043

983

925

820

776

60/1000/A

Medium High

1251

1198

1140

1089

1038

979

916

854

790

718

Medium Low

1081

1062

1015

964

917

871

819

767

710

634

 

 

Low

909

900

852

812

769

739

712

662

612

547

 

High

1492

1442

1378

1325

1243

1176

1075

966

849

655

60/1200/B

Medium High

1236

1201

1161

1139

1082

1011

919

830

715

590

Medium Low

986

950

961

916

872

831

757

703

600

510

 

 

Low

824

795

783

744

713

659

624

554

489

389

 

High

1597

1537

1484

1435

1370

1286

1230

1155

1075

925

80/1200/B

Medium High

1338

1307

1273

1223

1179

1123

1065

998

928

812

Medium Low

1113

1094

1077

1043

1008

972

924

868

803

798

 

 

Low

937

916

900

877

854

817

775

718

639

560

 

High

1919

1865

1802

1738

1671

1600

1517

1414

1322

1201

80/1600/C

Medium High

1532

1533

1513

1499

1465

1416

1352

1283

1198

1084

Medium Low

1232

1313

1291

1280

1250

1209

1207

1148

1055

937

 

 

Low

826

821

853

858

838

817

794

776

760

711

 

High

2529

2435

2338

2256

2162

2041

1920

1794

1654

1501

80/2200/C

Medium High

2166

2111

2070

2001

1927

1849

1719

1614

1499

1344

Medium Low

1697

1685

1664

1631

1586

1531

1466

1393

1315

1185

 

 

Low

1383

1377

1358

1336

1285

1244

1199

1147

1048

925

 

High

1909

1880

1823

1776

1706

1637

1562

1474

1375

1252

100/1600/C

Medium High

1465

1463

1469

1485

1477

1416

1386

1324

1250

1114

Medium

1190

1222

1216

1215

1224

1189

1158

1145

1087

996

 

 

Low

787

834

819

836

819

810

790

761

690

707

 

High

2284

2205

2114

2021

1934

1848

1752

1653

1505

1397

100/2000/C

Medium High

1967

1905

1824

1763

1712

1628

1551

1473

1379

1213

Medium Low

1610

1563

1513

1480

1430

1367

1319

1261

1101

1012

 

 

Low

1326

1304

1267

1232

1183

1143

1080

1003

871

798

 

High

2020

1994

1958

1878

1805

1740

1647

1560

1445

1294

120/1600/D

Medium High

1551

1559

1549

1520

1494

1451

1383

1334

1253

1145

Medium Low

1270

1267

1269

1269

1254

1227

1185

1121

1051

985

 

 

Low

932

916

905

894

876

828

803

725

754

696

 

High

2341

2245

2153

2072

1977

1876

1769

1642

1506

1306

120/2000/D

Medium High

2002

1952

1878

1823

1739

1657

1563

1458

1322

1185

Medium Low

1615

1579

1533

1473

1430

1368

1282

1186

1091

953

 

 

Low

1352

1295

1259

1245

1190

1141

1076

998

938

820

 

High

2412

2329

2247

2173

2047

1980

1887

1777

1655

1511

130/2000/D

Medium High

2040

2004

1948

1876

1786

1738

1656

1562

1461

1314

Medium Low

1614

1591

1549

1531

1459

1400

1335

1267

1180

1061

 

 

Low

1327

1294

1257

1224

1198

1171

1124

1036

944

848

NOTES:

1.Airflow expressed in standard cubic feet per minute (CFM). 2.Motor voltage at 115 V.

34

Johnson Controls Unitary Products

Page 34
Image 34
Johnson Controls TG9S'MP, GG9S'MP installation manual UIM-H-0712, Bottom Airflow Data SCFM

FAQ

What is the airflow data for models TG9S'MP and GG9S'MP?

The airflow data for different speeds and external static pressure can be found in Table 17 of the official manual.

What is the motor voltage for this blower performance data?

The motor voltage for the blower performance data is 115 V.

Where can I find more detailed information on blower performance for Johnson Controls Furnace?

You can refer to Table 17 in the official manual for detailed airflow data for different speeds and external static pressure.