ADJUSTMENT OF FAN CONTROL SETTINGS
Cooling - The airflow delivered by the furnace during cooling operation can be adjusted to match the cooling capacity of the A/C condensing unit. This is done by moving the COOL jumper on the control board to give the desired airflow.
Do not move the motor wires to different positions on the furnace control board!
The jumper has four positions, which will deliver sufficient airflow in cooling mode for the cooling capacities shown in the table below. The CFM delivery on each jumper position is shown in Table 13.
TABLE 13: Cooling Airflow - A/C Capacity in Tons
Models |
| Jumper Position |
| |
|
|
|
| |
| A | B | C | D |
60/1200 | 3 | 2 | ||
80/1200 | 3 | 2 | ||
80/1600 | 4 | 3 | ||
100/1600 | 4 | 3 | ||
100/2000 | 5 | 4 | 3 | |
120/2000 | 5 | 4 | 3 |
Continuous Fan Operation - The airflow delivered by the furnace dur- ing continuous fan operation can be adjusted as desired. This is done my moving the FAN jumper on the control board to give the desired air- flow.
Do not move the motor wires to different positions on the furnace control board!
The jumper has three positions. The "A" position delivers maximum air- flow, 100% of the blower capacity. Position "B" delivers approximately 70% of the blower capacity. And Position "C" delivers minimum airflow, approximately 40% of the blower capacity.
HUMIDIFIER | EAC | ZONING |
TERMINALS | TERMINALS | JUMPER |
BLACK | BLOWER |
| BLUE | BLOWER | YELLOW | BLOWER | RED | BLOWER |
120VAC 120VAC | XFORMER | NEUTRAL NEUTRAL | XFORMER GROUND WHITE | BLOWER |
|
|
| HUMIDIFIER |
| 24VAC | MODULATE COIL | GAS VALVE |
|
|
|
|
|
|
| PRIMARY | AUX |
|
|
| TEMP | |
|
| LIMIT | LIMIT |
| AIR SW |
| SENSOR |
|
|
|
| ROD | VOLTAGE FLAME |
| ||||
|
|
|
|
|
|
|
|
|
| |
NEUTRAL INDUCER | NEUTRALHOT | IGNITER | NEUTRALHOT | FLAME EACEAC | NEUTRALHOT | ZONE CONTROL |
| NO YES | EXT PRESSURE SENSOR |
|
HOT |
|
|
|
|
|
|
|
|
|
|
|
|
|
| PLUG |
| PUMP |
|
| ||
|
| COMPLO | COMPHI | ID |
| HEAT | YES NO | COOL | MLMH H | BUTTON |
|
| O DHUM Y1 Y/Y2 HUMIDISTATW | R | G | C | TEST | ||||
|
|
|
|
|
|
| NO YES | FANCONTATR | L |
|
|
|
|
|
|
|
|
|
| LMH |
|
|
|
|
|
|
|
|
|
| +10F |
|
|
|
|
|
|
|
|
|
| NOM |
|
|
|
|
|
|
|
|
|
| 10F- |
|
|
|
|
|
|
|
|
|
| BUTTON RERRO |
HEAT PUMP JUMPER
COOLING
SPEED
JUMPER
CONTINUOUS FAN SPEED JUMPER
TEST
BUTTON
DIAGNOSTIC
LIGHT
FIGURE 30: Furnace Control Board
LOW |
|
|
VOLTAGE | HUMIDISTAT | LAST ERROR |
TERMINALS | JUMPER | BUTTON |
SECTION IX: SAFETY CONTROLS
CONTROL CIRCUIT FUSE
A
BLOWER DOOR SAFETY SWITCH
This unit is equipped with an electrical interlock switch mounted in the burner compartment. This switch interrupts all power at the unit when the panel covering the blower compartment is removed.
Electrical supply to this unit is dependent upon the panel that covers the blower compartment being in place and properly positioned.
Main power to the unit must still be interrupted at the main power disconnect switch before any service or repair work is to be done to the unit. Do not rely upon the interlock switch as a main power dis- connect.
Blower and burner must never be operated without the blower panel in place.
ROLLOUT SWITCH CONTROLS
These controls are mounted on the burner assembly. If the temperature in the burner area exceeds its set point, the ignition control and the gas valve are