| 12 |
Heightin Feet | 9 |
5 | |
Max. One 90° | |
CollarVentFrom | |
| Elbow |
12
9
Feetin CollarVent 5
HeightFrom
1
Max. One 90°
Elbow
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| 3 |
|
|
|
|
|
|
|
|
|
|
|
| 5 | 10 | 12 | ||||||||||
|
|
|
|
|
| ||||||||||
|
|
|
|
|
| Horizontal Run in Feet | |||||||||
|
|
|
|
|
| ||||||||||
|
|
|
|
|
|
Figure 15. Horizontal termination -5/8 pipe.
3 | 5 | 10 | 12 |
Horizontal Run in Feet
Figure 16. Horizontal Termination - 4/6 Pipe. Minimum 1 ft. rise required.
Horizontal Termination Clearance
Figure 17. Vent Terminal Clearances - National Fuel Gas Code.
A = Clearance above grade, veranda, porch , deck, or balcony : *12 inches (30 cm) minimum.
B = Clearance to window or door that may be opened:
Min. 9 inches, U.S. / *12 inches (30 cm) CAN.
We recommend 12in. minimum to prevent condensa- tion on the window.
C = Clearance to permanently closed window:
Min. 9 inches, U.S. / *12 inches (30 cm) CAN
We recommend 12in. minimum to prevent condensa- tion on the window.
D = Vertical clearance to ventilated soffit located above the terminal within a horizontal distance of 2 feet (60 cm) from the centerline of the terminal: 18 inches
(46 cm) minimum.
E = Clearance to unventilated soffit: *12 inches (46 cm) minimum.
F = Clearance to outside corner: Min. 9 inches, U.S. / *12 inches (30 cm) CAN. We strongly recommend 12 inches, particularly where windy conditions pevail.
*As specified in CGA B149 Installation Codes. Note: Local Codes and Regulations may require different clearances.
G = Clearance to inside corner: Min. 6 inches, U.S. / *12 inches (30 cm) CAN. We strongly recommend 12 inches, particularly where windy conditions pevail.
H = *Not to be installed above a meter/regulator assembly within 3 feet (90 cm) horizontally from the
I = Clearance to service regulator vent outlet:
3 feet, U.S. / 6 feet (1.8 m), CAN.
J = Clearance to nonmechanical air supply inlet to building or the combustion air inlet to any other appliance:
*12 inches (30 cm) minimum.
K = Clearance to a mechanical air supply inlet: *6 feet (1.8 m) minimum.
L = ** Clearance above paved sidewalk or a paved driveway located on public property: *7 feet (2.1 m) min.
M = Clearance under veranda, porch, deck, or balcony:
*12 inches (30 cm) minimum. 1
**A vent shall not terminate directly above a sidewalk or driveway which is located between two single family dwellings and serves both dwellings.*
1Only permitted if veranda, porch, deck, or balcony, is fully open on a minimum of two sides beneath the floor.*