Jotul GZ 550 DV II manual Horizontal Termination Clearance, Heightin Feet

Models: GZ 550 DV II

1 32
Download 32 pages 22.29 Kb
Page 11
Image 11
Heightin Feet

 

12

Heightin Feet

9

5

Max. One 90°

CollarVentFrom

 

Elbow

12

9

Feetin CollarVent 5 12

HeightFrom

1 Figure 15. Horizontal termination -5/8 pipe.

Max. One 90°

Elbow

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

3

 

 

 

 

 

 

 

 

 

 

 

 

5

10

12

 

 

 

 

 

 

 

 

 

 

 

 

Horizontal Run in Feet

 

 

 

 

 

 

 

 

 

 

 

 

Figure 15. Horizontal termination -5/8 pipe.

3

5

10

12

Horizontal Run in Feet

Figure 16. Horizontal Termination - 4/6 Pipe. Minimum 1 ft. rise required.

Horizontal Termination Clearance

Figure 17. Vent Terminal Clearances - National Fuel Gas Code.

A = Clearance above grade, veranda, porch , deck, or balcony : *12 inches (30 cm) minimum.

B = Clearance to window or door that may be opened:

Min. 9 inches, U.S. / *12 inches (30 cm) CAN.

We recommend 12in. minimum to prevent condensa- tion on the window.

C = Clearance to permanently closed window:

Min. 9 inches, U.S. / *12 inches (30 cm) CAN

We recommend 12in. minimum to prevent condensa- tion on the window.

D = Vertical clearance to ventilated soffit located above the terminal within a horizontal distance of 2 feet (60 cm) from the centerline of the terminal: 18 inches

(46 cm) minimum.

E = Clearance to unventilated soffit: *12 inches (46 cm) minimum.

F = Clearance to outside corner: Min. 9 inches, U.S. / *12 inches (30 cm) CAN. We strongly recommend 12 inches, particularly where windy conditions pevail.

*As specified in CGA B149 Installation Codes. Note: Local Codes and Regulations may require different clearances.

G = Clearance to inside corner: Min. 6 inches, U.S. / *12 inches (30 cm) CAN. We strongly recommend 12 inches, particularly where windy conditions pevail.

H = *Not to be installed above a meter/regulator assembly within 3 feet (90 cm) horizontally from the center-line of the regulator.

I = Clearance to service regulator vent outlet:

3 feet, U.S. / 6 feet (1.8 m), CAN.

J = Clearance to nonmechanical air supply inlet to building or the combustion air inlet to any other appliance:

*12 inches (30 cm) minimum.

K = Clearance to a mechanical air supply inlet: *6 feet (1.8 m) minimum.

L = ** Clearance above paved sidewalk or a paved driveway located on public property: *7 feet (2.1 m) min.

M = Clearance under veranda, porch, deck, or balcony:

*12 inches (30 cm) minimum. 1

**A vent shall not terminate directly above a sidewalk or driveway which is located between two single family dwellings and serves both dwellings.*

1Only permitted if veranda, porch, deck, or balcony, is fully open on a minimum of two sides beneath the floor.*

11

Page 11
Image 11