•Brick or modular block must be a minimum of 4” (10 cm) nominal thickness. Stone construction must be at least 12” (30 cm) thick.
•A
•An existing chimney must be inspected by a professional licensed chimney sweep, fire official, or code officer to ensure that the chimney is in proper working order.
•No other appliance may be vented into the same flue.
•An airtight
Prefabricated Chimneys
A prefabricated metal chimney must be tested and listed for use with solid fuel burning appliances. High Temperature (HT) Chimney Standard UL 103 for the U.S. and High Temperature Standard ULC
The manufacturer’s installation instructions must be followed precisely. Always maintain the proper clearance to combustibles as established by the pipe manufacturer. This clearance is usually a minimum of 2”, although it may vary by manufacturer or for certain chimney components.
Chimney Height
The chimney must be at least 3 feet (92 cm) higher than the highest point where it passes through the roof and at least 2 feet (61 cm) higher than the highest part of the roof or structure that is within 10 feet (3.05 m) of the chimney, measured horizontally. See figure 3.
Chimneys shorter than 14 feet (4.27 m) may not provide adequate draft. Inadequate draft can result in smoke spillage when loading the stove, or when the door is open. Poor draft can also cause back puffing (ignition of gas build- up inside the firebox) and sluggish performance. The minimum height does not, in itself, guarantee proper chimney performance.
Excessive chimney height can promote
Wall Pass-Throughs
In the U.S.
The National Fire Protection Association’s publication, NFPA 211, Standard for Chimneys, Fireplaces, Vents and Solid Fuel Burning Appliances permits four methods for passing through a combustible wall. Before proceeding with any method be sure to consult with your local building officials to discuss any local code requirements.
USA/Canada
Common Method:
•See figures 4 and 5. Remove all combustible materials from the
•The opening must be filled with at least 12” (30.5 cm) of brick around a fireclay liner. The liner must be ASTM C35 or equivalent, having a minimum wall thickness of 5/8” (16 mm).
•The
•It will be necessary to cut wall studs, install headers, and construct a sill frame to maintain the proper dimensions and to support the weight of the brick.
•The bricks must be solid brick with a minimum of 3 ½ inches thick (nominal 4” / 102 mm).
•Refractory mortar must be used at the junction of the chimney and the
In Canada
The installation must conform to
Common Method:
•This method requires the removal of all combustible materials from at least 18” (45.7 cm) around the chimney connector’s proposed location. A 6”round liner requires a minimum opening 43” x 43” (109.2 x 109.2) square.
•Locate the
•The space that is cleared of combustible materials must remain empty. Sheet metal panels can be used to cover the area. However, when using a panel on both sides of the wall, each cover must be installed on noncombustible spacers at least 1” from the wall. If one panel of sheet metal is to be used it may be installed flush to the wall.
See section 5.3.1 and 5.3.2 of CAN/CSA -
5