40 Gal. Water Heater: Align the reducer flue over top of baffle as

shown in Figure 19 (NOTE: reducer flue must be installed on 40 gal. water heater above elevation 5,400 Ft. (1,646 m) from sea level).

40 & 50 Gal. Water Heaters: Align the legs of the draft hood with the slots provided. Insert the legs and secure the draft hood to the water heater's top with the four screws provided as shown

in Figure 19. Do not alter the draft hood in any way. If you are replacing an existing water heater, be sure to use the draft hood supplied with this water heater.

Z223.1(NFPA 54)-current edition.

The connector must be installed above the extreme bottom of the chimney to prevent potentially blocking the flue gases.

The connector must be firmly attached and sealed to prevent it from falling out.

To aid in removing the connector, a thimble or slip joint may be used.

The connector must not extend beyond the inner edge of the chimney as it may restrict the space between it and the opposite wall of the chimney (Figure 20).

Vent Pipe Size

It is important that you follow the guidelines in these instructions for sizing a vent pipe system. If a transition to a larger vent size is required, the vent transition connection must be made at the draft hood outlet.

Vent Connectors

1.Type B, Double wall, U.L. Listed Vent Pipe.

2.Single walt Vent Pipe.

Maintain the manufacturer's specified minimum clearance from combustible materials when using type B double walt vent pipe. Vent connectors made of type B, double walt vent pipe material may pass through walls or partitions constructed of combustible material if the minimum listed clearance is maintained.

Maintain a six inch minimum clearance from all combustible materials when using single walt vent pipe.

IMPORTANT: Single wall vent pipe cannot be used for water heaters located in attics and may not pass through attic spaces, crawl spaces or any confined or inaccessible location. A single wall metal vent connector cannot pass through any interior wall. When installing a vent connector, please note the following (See Figures 20-22):

Install the vent connector avoiding unnecessary bends, which create resistance to the flow of vent gases.

Install without dips or sags with an upward slope of at least 1/4-inch per foot.

Joints must be fastened by sheet metal screws or other approved means. It must be supported to maintain clearances and prevent separation of joints and damage.

The length of the vent connector cannot exceed 75% of the vertical vent height.

The vent connector must be accessible for cleaning, inspection, and replacement.

Vent connectors cannot pass through any ceiling, floor, firewall, or fire partition.

It is recommended (but not mandatory) that a minimum 12 inches of vertical vent pipe be installed on the draft hood prior to any elbow in the vent system.

IMPORTANT: Existing vent systems must be inspected for obstructions, corrosion, and proper installation.

Chimney Connection

IMPORTANT: Before connecting a vent to a chimney, make sure the chimney passageway is clear and free of obstructions. The chimney must be cleaned if previously used for venting solid fuel appliances or fireplaces. Also consult local and state codes for proper chimney sizing and application or, in the absence

of local and state codes, the "National Fuel Gas Code", ANSI

 

 

Above Any Object

3 FT.

Within

10 FT. Horizontally

Minimum

 

 

Support StraE

 

 

Maintain

 

 

Clearance*

 

 

f

Do

Not Extend

 

 

Vent

Beyond Edge

 

Of Chimney

Connector

Chimney Termination Vent System

FIGURE 20.

Do not terminate the vent connector in a chimney that has not been certified for this purpose. Some local codes may prohibit the termination of vent connectors in a masonry chimney.

Vertical Exhaust Gas Vent

Vertical exhaust gas vents must be installed with U.L. listed type B vent pipe according to the vent manufacturer's instructions and the terms of its listing.

It must be connected to the water heater's draft hood by a listed vent connector or by directly originating at the draft hood opening.

Vertical gas vents must terminate with a listed cap or other roof assembly and be installed according to their manufacturer's instructions.

Gas vents must be supported to prevent damage, joint separation, and maintain clearances to combustible materials (Figures 21 and 22).

IMPORTANT: This gas vent must be terminated in a vertical position to facilitate the removal of the burnt gases.

An unused chimney flue or masonry enclosure may be used as a passageway for the installation of a gas vent (Figure 22).

Common (combined) venting is allowable with vertical type B vent systems and lined masonry chimneys as long as proper draft for the water heater is established under all conditions of operation. CAUTION: DO NOT common vent this water heater with any power vented appliance.

Figures 20-22 are examples of vent pipe system installations and may or may not be typical for your specific application. Consult the "National Fuel Gas Code", NFPA 54, ANSI Z223.1-current edition and the guidelines set forth by prevailing local codes.

20

Page 20
Image 20
Kenmore 153.33264, 153.33262 manual Vent Pipe Size, Chimney Connection, Vertical Exhaust Gas Vent, Vent Connectors

153.33262, 153.33264 specifications

The Kenmore 153.33262 and 153.33264 are highly versatile and efficient portable air conditioners designed to provide optimal cooling solutions for indoor spaces. These models stand out in their class due to their advanced features, technologies, and user-friendly characteristics, making them suitable for a variety of environments, from small apartments to large rooms.

One of the primary features of both the Kenmore 153.33262 and 153.33264 is their high cooling capacity. With powerful BTUs, they can effectively cool spaces up to a specified square footage. This capability ensures that users can maintain a comfortable indoor climate even during the hottest summer months. Their energy efficiency is another notable aspect, allowing homeowners to enjoy cooler air without incurring exorbitant energy bills.

The two models are equipped with various modes of operation, including cooling, fan, and dehumidifying modes. This multifunctionality allows users to customize their comfort based on prevailing weather conditions. For instance, the dehumidifying mode effectively reduces excess moisture in the air, creating a more comfortable environment, particularly in humid regions.

Both air conditioners come with a user-friendly digital interface that features an easy-to-read LED display. The interface allows for straightforward adjustments to the temperature, fan speed, and operating modes. Furthermore, remote control functionality enhances convenience, enabling users to change settings from across the room.

In terms of technology, these models incorporate a self-evaporating system that minimizes the need for manual water drainage. This feature is particularly advantageous for users who prefer low-maintenance options. Additionally, both units feature a washable air filter, designed to capture dust and allergens, improving air quality and ensuring that the units operate efficiently.

Portability is another significant characteristic of the Kenmore 153.33262 and 153.33264. Built-in caster wheels and side handles allow for easy movement from room to room, making them ideal for temporary cooling needs. The easy installation process and included window exhaust kit mean users can set up the units quickly without requiring professional assistance.

In conclusion, the Kenmore 153.33262 and 153.33264 portable air conditioners offer a robust combination of high cooling performance, energy efficiency, and user-friendly features. Their advanced technologies and versatile functionalities make them an ideal choice for those seeking effective indoor air conditioning solutions.