Kenmore 153.33262 T&P Relief Valve and Pipe Insulation, The Temperature, Pressure Relief Valve

Models: 153.33262 153.33264

1 44
Download 44 pages 3.4 Kb
Page 23
Image 23
The Temperature

For protection against excessive pressures and temperatures,

a temperature and pressure relief valve must be installed in the opening marked "T & P RELIEF VALVE" (see Figure 25). This valve must be design certified by a nationally recognized testing laboratory that maintains periodic inspection of the production of listed equipment or materials as meeting the requirements for Relief Valves for Hot Water Supply Systems, ANSI Z21.22. The function of the temperature and pressure relief valve is to discharge water in large quantities in the event of excessive temperature or pressure developing in the water heater. The valve's relief pressure must not exceed the working pressure of the water heater as stated on the rating plate.

IMPORTANT: Only a new temperature and pressure relief valve should be used with your water heater. Do not use an old or existing valve as it may be damaged or not adequate for the working pressure of the new water heater. Do not place any valve between the relief valve and the tank.

4.Locate the hot water (outlet) & cold water (inlet) pipes to the water heater.

5.Locate the slit running the length of a section of pipe insulation.

6.Spread the slit open and slip the insulation over the cold water (inlet) pipe. Apply gentle pressure along the length of the insulation to ensure it is fully seated around the pipe. Also ensure that the base of insulation is flush with the water heater. Once seated, secure the insulation with duct tape, electrical tape, or equivalent.

7.Repeat steps 5 through 6 for the hot water (outlet) pipe.

8.Add additional sections of pipe insulation as needed.

The Temperature

& Pressure Relief Valve:

_

Lever

 

 

Must not be in contact with any electrical part.

Must be connected to an adequate discharge line.

-T&P Relief V_

Must not be rated higher than the working pressure shown

 

on the rating

plate of the water heater.

T&P

Relief Valve

 

Drain

Line

The

Discharge

Line:

 

 

/

Must not be

smaller

than the pipe size of the relief

valve or

T&P Relief Valve Insulation

 

have any reducing coupling installed in the discharge line.

 

Must not be capped,

blocked, plugged or contain

any valve

FIGURE 26.

 

 

 

 

 

between the relief valve and the end of the discharge line. Must terminate a maximum of six inches above a floor drain or external to the building. In cold climates, it is recommend- ed that the discharge pipe be terminated at an adequate drain inside the building.

Must be capable of withstanding 250°F (121°C) without dis- tortion.

Must be installed to allow complete drainage of both the valve and discharge line.

T&P Relief Valve and Pipe Insulation

1, Locate the temperature and relief valve on the water heater (also known as a T&P Relief Valve, Figure 26).

2.Locate the slit running the length of the insulation.

3Spread this slit open and slip it up under the T&P Relief Valve. See Figure 26. Apply gentle pressure to the insulation to ensure it is fully seated on the T&P Relief Valve. Once sealed secure the insulation with a section of duct tape, electrical tape, or equivalent.

IMPORTANT: The insulation or tape must not block the discharge opening or hinder access to the manual relief lever. Ensure a discharge pipe is installed into the T&P valve discharge opening per the instructions manual.

23

Page 23
Image 23
Kenmore 153.33262, 153.33264 T&P Relief Valve and Pipe Insulation, The Temperature, Pressure Relief Valve, Discharge, Line