TP-6810 11/13 25Section2 GeneratorSet Operation

2.6.5 Event Log

The event log displays up to 1000 controller faults and
notices,starting with the most recent event. Eventsare
numbered1 --1000,with 1 being the most recent. Each
event is displayed with the date and time of the event,
thenumber of the event, a code to indicate whether the
event was a warning (W), shutdown (S), or
informationalnotice ( I), theengine hours at the time of
the event, and the event description.
Procedure to View Event History
1. Press Select to enter the main menu.
2. Pressthedownarrow to step down to the event log.
3. Press Select to display the most recent event.
4. Press the down arrow to step to the next event.
5. Usetheup and down arrow buttons to view events.
6. Press the Select button to exit the event log.
Tostop viewing the event history before the last event,
press the select button toreturn to the main menu.
tp6810
Event Log ---->
DateMO/DA/YEAR
timeHR:MN
eventnumber, W/S/I, engine hours
eventname
PressUP and Down arrow
buttonsto scroll through events
DateMO/DA/YEAR
timeHR:MN
eventnumber, W/S/I, engine hours
eventname
PressSelect button at any time to
returnto the main menu.
Eventcodes:
W=Warning
S= Shutdown
I= Informational Notice
Figure 2-6 Event Log
2.7 Model RXT Transfer SwitchOperation
The RDC2 generator set/transfer switch controller
manages automatic transfer switch (ATS) functions
whenconnected to a KohlerrModel RXT transfer switch
through the ATS interface board. Refer to the Model
RXT Operation/Installation Manual for information
about the transfer switch operation.

2.7.1 Source Availability

The Model RXT transfer switch supplies voltage
sensing data to the RDC2 controller through the ATS
interface board. If the source voltage falls below the
undervoltage dropoutsetting, thesource is considered
to have failed. SeeFigure 2-7.
Item Setting
Accuracy ±5%
Undervoltage Dropout 90% of Pickup
Undervoltage Pickup 90%of Nominal
Figure 2-7 VoltageSensing Parameters
The RDC2 controller also has a set of power system
LEDsbelow the pushbuttons. Thepower system LEDs
indicate which power sources are available and which
source is supplying power to the building. See
Figure 3-1.
Note: The power system LEDs operate only if a Model
RXT transfer switch is connected. Theywill not
operateif a Model RDT or RSB transfer switch is
used.