5.5 Generator Set Troubleshooting
Figure 5-1 contains generator set troubleshooting, diagnostic, and repair information. Check for loose connections before replacing parts.
Problem | Possible Cause | Corrective Action | |
|
|
| |
The generator | Battery weak or dead. | Recharge or replace the battery. | |
set does not |
|
| |
Battery connections reversed or poor. | Check the connections. | ||
crank. | |||
|
| ||
Blown fuse(s). | Replace the fuse. Contact an authorized Kohler | ||
| |||
|
| distributor/dealer for service if fuse blows repeatedly. | |
|
|
| |
| Generator set is OFF. | Press the RUN button to start the engine or press AUTO | |
|
| to allow remote starting. | |
|
|
| |
The generator | Air cleaner clogged. | Clean and/or replace the air cleaner. | |
set cranks but |
|
| |
Battery weak or dead. | Recharge or replace the battery. | ||
does not start, | |||
|
| ||
Battery connection poor. | Clean and tighten the battery connections. | ||
starts hard, | |||
|
| ||
lacks power, or | Spark plug wire connection loose. | Check the spark plug wires. | |
operates |
|
| |
Low oil pressure shutdown. | Check for oil leaks. Check the oil level and add oil if | ||
erratically. | |||
| necessary. | ||
|
| ||
|
|
| |
| Fuel pressure insufficient. | Check the fuel supply and valves. | |
|
|
| |
| Engine fuse blown. | Replace the fuse. If the fuse blows again, contact an | |
|
| authorized Kohler distributor/dealer. | |
|
|
| |
| Engine malfunction. | Contact an authorized Kohler distributor/dealer. | |
|
|
| |
No AC output. | AC circuit breaker in the OFF position. | Place the circuit breaker in the ON position. | |
|
|
| |
| AC circuit breaker tripping because of overload. | Reduce the load on the generator set. | |
|
|
| |
| AC circuit breaker tripping because of short | Contact an authorized Kohler distributor/dealer for | |
| circuit. | service. | |
|
|
| |
| Engine fuse blown. | Replace the fuse. Contact an authorized Kohler | |
|
| distributor/dealer for service if fuse blows repeatedly. | |
|
|
| |
Low output or | Generator set overloaded. | Reduce the load. | |
excessive drop |
|
| |
in voltage. |
|
| |
|
|
| |
Generator set | Low oil pressure shutdown. | Check for oil leaks. Check the oil level and add oil if | |
stops suddenly. |
| necessary. | |
|
|
| |
| Out of fuel. | Check fuel supply. | |
|
|
| |
| Overcrank shutdown. | Reset the controller. If the overcrank fault occurs again, | |
|
| contact an authorized Kohler distributor/dealer. | |
|
|
| |
| Blown fuse(s). | Replace the fuse. If the fuse blows again, contact an | |
|
| authorized Kohler distributor/dealer. | |
|
|
| |
| Overspeed shutdown. | Reset the controller. If the overspeed fault occurs again, | |
|
| contact an authorized Kohler distributor/dealer. | |
|
|
| |
| Generator set is OFF. | Press the RUN button to start the engine or press AUTO | |
|
| to allow remote starting. | |
|
|
| |
| Remote stop command received from a remote | Check the remote switch position. | |
| switch, ATS, or OnCuer. |
| |
|
|
| |
| Engine malfunction. | Contact an authorized Kohler distributor/dealer. | |
|
|
| |
Fans run after | The fans continue to run for 2 minutes after the | None. | |
engine shuts | engine shuts down to evacuate the engine |
| |
down. | compartment. |
|
Figure 5-1 General Troubleshooting Chart