VENT TERMINAL
EXHAUSTINTAKE
SLOPE THE VENT TERMINAL HORIZONTAL RUN DOWNWARD THE OUTSIDE TO DRAIN OUT ANY CONDENSATE
INTAKE AIR
EXHAUST AIR
EXTERIOR WALL
SLOPE DOWNWARD 1/4" (6mm)
PER FOOT (m) TO DRAIN ANY
CONDENSATE OUTSIDE
| SUPPORT STAP EVERY |
COUPLING WITH | 5 FT. (1.5m) MIN. |
HOSE CLAMPS | EXHAUST AIR |
ELBOW WITH CLAMPS
INTAKE AIR
INTERIOR WALL
SHROUD SIDE
FILTER
TEMPERATURE CONTROL DOOR
Figure 11
Figure 12
Reassembly and Resealing Vent-Air Intake System
When
Condensate Removal (Figures 11 and 12)
The condensate drain kit is used in conjunction with DVE and
Whenever a vertical vent run, in a heated room [10 ft. (3m) or more for
Whenever a horizontal vent run is used, where local codes allow, you can slope the exhaust pipe downward, to the outside, 1/4" (6mm) per foot (305mm). The downward slope on the exhaust pipe will allow any condensate to flow out of the exhaust pipe. If local codes prohibit condensate from draining to the outside and the appliance produces condensate you must purchase condensate drain kit, part number
elbow assemblies are
air vent pipe to the mounting plate.
Page 12 |