HEATING SEQUENCE OF OPERATION WITH SINGLE-STAGE THERMOSTAT

NOTE − THIS FURNACE FUNCTIONS WITH TWO INDEPENDENTLY CONTROLLED HEAT SECTIONS. THE GRAY BOXES INDICATE COMPONENTS WHICH EFFECT BOTH HEAT SECTIONS SIMULTANEOUSLY.

NORMAL HEATING MODE

POWER ON

THERMOSTAT CALLS FOR HEAT

(W1 ENERGIZED)

K13 AND K19 RELAY ENERIZED.

(W1 AND W2 OF FURNACE

TERMINAL STRIP JUMPERED.)

A3 (A12) IGNITION CONTROL LED ON.

IS THE S10 (S99) HIGH LIMIT CLOSED?

YES

IS THE S47 (S69) ROLLOUT SWITCH CLOSED?

YES

IS THE B6 (B15) COMBUSTION

AIR BLOWER ON?

YES

ABNORMAL HEATING MODE

 

NO

DETERMINE WHY AUTOMATIC-RESET

 

 

 

 

 

S10 (S99) HIGH LIMIT OPEN.

 

 

 

 

 

 

 

 

 

NO

CHECK VENTING SYSTEM

 

 

 

 

 

OPERATION/BLOCKAGE BEFORE

 

 

 

 

 

 

 

 

 

 

RESETTING THE MANUALLY-RESET S47

 

 

 

 

 

(S69) ROLLOUT SWITCH.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

NO

CHECK K13−1 CONTACT OPERATION AND

 

 

 

 

 

WIRING TO B6 (B15) COMBUSTION AIR

 

 

 

 

 

 

 

 

 

 

BLOWER?

 

 

IS THE S18 (S45) COMBUSTION AIR BLOWER PROVING SWITCH CLOSED?

YES

B6 (B15) COMBUSTION AIR BLOWER

PREPURGE FOR 30 SECS.

8 SEC TRIAL FOR IGNITION − START IGNITION TRAIL, GV1 (GV3) GAS VALVE OPENS ON LOW HEAT AND AFTER A 3 SEC. DELAY OPENS ON HIGH HEAT. IS FLAME SENSED WITHIN 8 SECS?

YES

K56 (K57) RELAY ENERGIZED. K25 CIRCUIT BOARD ENERGIZED. SYSTEM BLOWERS ON AFTER 45 SEC DELAY.

YES

FLAME SENSE OK?

NO

CHECK SENSING TUBE FOR BLOCKAGE

AND S18 (S45) SWITCH FOR PROPER

 

 

 

OPERATION.

 

 

 

 

 

NO

 

 

 

 

 

GV1 (GV3) GAS VALVE CLOSED, SPARK

NO

OFF. INCREMENT TRAIL REGISTER.

 

(DURING RETRY PERIOD LED FLASHES

 

 

.5 SEC. ON AND 2.5 SEC. OFF. ARE THE

 

THREE TRIALS COMPLETE?

 

 

 

 

 

 

 

YES

 

 

 

 

 

LOCKOUT OCCURS. TO RESET A3 (A12) IGNITION CONTROL MOVE THERMOSTAT SWITCH FROM HEAT TO OFF TO HEAT.

NO

CHECK BELT.

CHECK RELAYS.

NO

YES

CONTINUED NEXT PAGE